12
RECHECK CONTROL SETTINGS
Now that all the ceramic fuel effects are in position, the control operation must be fully rechecked.
Make sure that the isolating valve at the inlet elbow is open.
Depress the control knob and turn anti-clockwise partially towards the “
PILOT/IGN
” position. A spark
should be generated at the pilot while turning. The spark should ignite the pilot. Check that the pilot flame is
visible.
When pilot ignition has been achieved, keep the control knob depressed for approximately ten seconds to allow
the thermocouple probe to warm up and then release it. If the pilot does not remain alight, ensure that the pilot
orifice is clear.
When the pilot is alight and stable, partially depress the knob and turn to “
LOW
”. The pilot should then light
the main burner at its low setting. There may be a delay of up to four seconds between the pilot lighting and
ignition of the gas at the main burner. This is normal and is due to the time required to fill the main burner
compartment with sufficient gas for ignition.
When the burner is operating properly, partially depress the knob and gradually turn it anti-clockwise. The
burner flames should gradually increase until the knob reaches the “
HIGH
” position.
Partially depress the control knob and turn back the “
PILOT/IGN
”. The main burner flames should be
extinguished but the pilot should remain alight.
Partially depress the control knob and turn to “
OFF
” the pilot should be extinguished.
CHECK FOR SPILLAGE
A spillage check must be made before leaving the installed appliance with the customer. Make this
check with the appliance fully installed with the ceramic fuel
effects and front surround in position.
Close all doors and windows in the room containing the appliance.
Light the appliance and turn the control knob to “
HIGH
”.
Leave the appliance on for five minutes.
Place the smoke match into the appliance canopy (See Fig.15)
The installation is satisfactory if the smoke is drawn into the appliance. If
the smoke is not drawn into the appliance, leave the appliance alight at the
maximum setting for a further ten minutes and then repeat the test. If
smoke is still not drawn into the appliance, inspect the sealing to the
fireplace surround. If smoke is still not drawn into the appliance,
Disconnect the appliance and seek expert advice.
If the above test is satisfactory, open all internal connecting doors,
hatches, etc., in the room. Keep all doors and windows that open to the
outside of the building closed. Recheck for spillage as above. If an extractor fan is installed in the same room as
the appliance or a connecting room, check that spillage does not occur with the fan operating and all doors and
other openings between the fan and the appliance open.
FLAME SUPERVISION & SPILLAGE MONITORING SYSTEM
This pilot unit incorporates a system which will automatically shut off the gas supply if the pilot flame goes out
or if there is insufficient oxygen due to spillage or lack of ventilation.
This monitoring system must not be adjusted, bypassed or put out of operation.
This monitoring system, or any of its parts, must only be exchanged using Valor Authorised parts.
Figure 15 Spillage check