18
Venting
How to Read the Venting Chart
The chart below applies to roof or wall termination
.
1.
The total length of the vent pipe cannot exceed 40
feet (12.2 m).
2.
The minimum vertical height with roof termination is
6 feet (1.83 m).
3. Any combination of rise and run can be used as
long as they are within the allowable limits shown
on the chart below.
4.
A maximum of 4 x 90 degrees elbows—or
equivalent (2 x 45 degr. = 90 degr.)—can be used.
5.
Each 90 degrees elbow installed on the horizontal
plane is equivalent to a 3 feet horizontal pipe;
therefore, 3 feet must be subtracted from allowable
horizontal run. (45 degrees elbow is equivalent to
18 inches horizontal pipe.)
6.
All horizontal pipe runs must be graded 1/4 inch per
foot upwards in the direction of the exhaust fl ow.
The fi nal pipe length, when terminating through the
wall may be graded downwards slightly to prevent
water migration.
7.
Co-linear venting is
not allowed
.
8. A restrictor is required for many installations—see
next section.
2
4
6
8
10
12
14
16
18
20
Example 1
V Value = V1 (6’) + V2 (6’) + V3 (2’)= 14’
H Value = H1 (3’) + H2 (3’) = 6’
#2 Restrictor position required
VERTICAL
RISE (ft)
HORIZONTAL RUN (ft)
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
Venting Chart
4 x 90º ELBOWS
MAXIMUM (or equivalent)
#4 Restrictor
Example 1
NO INSTALLATION
NO INSTALLATION
V1
V2
V3
H1
H2
#3 Restrictor
#2 Restrictor
#1 Restrictor
Max. 24” pipe if
min. vertical rise
is used
Min. 12”
pipe
Max. 6” pipe
if min. vertical
rise is used
45º elbow
directly on
fl ue collar
Min. 2’
before
elbow
No Restrictor
Allowable Vent
Confi gurations
All around
vertical
pipe
Top of
horizontal
pipe
Bottom & sides
of horizontal pipe
1”
3”
1”
MINIMUM
VERTICAL
RISE: 2’