remain alight. Depress the control knob slightly and turn back (clockwise) to turn OFF.
This will extinguish the pilot.
14.2
Check For Spillage
1.
Close all doors and windows in the room containing the appliance.
2.
Light the appliance and set the control to the ‘High’ position.
3.
Leave the appliance on for five minutes.
4.
The smoke match should be placed horizontally into the hotbox at the right hand side.
(See figure 39).
The installation is satisfactory if the smoke is drawn into the appliance.
If the smoke is not drawn into the appliance leave the appliance alight at the maximum
setting for a further ten minutes and then repeat the test. If the smoke is still not drawn
into the appliance inspect the sealing to the fireplace surround. If the sealing is
satisfactory but the appliance is installed with the flue restrictor (See section 9 point 14)
remove the restrictor, reseal the appliance and retest. If smoke is still not drawn into the
appliance
disconnect the appliance and
seek expert advice.
5.
If the above test is satisfactory open all
internal connecting doors, hatches, etc. in
the room. Keep all doors and windows
that open to the outside of the building
closed. Recheck for spillage as above. If
an extractor fan is installed in the same
room as the appliance or a connecting
room, check that spillage does not occur
with the fan operating and all doors and
other openings between the fan and the
appliance open.
If the smoke is drawn into the appliance,
continue with the installation. If the test is
not satisfactory
disconnect the appliance
and advise the customer of the cause of
failure
.
Page 35
INSTALLER GUIDE
A spillage check must be made before leaving the installed appliance with the
customer. Make this with all the ceramic pebbles and firefront surround in
position
.
Figure 39. Smoke match tube position