VALLOX 75/95 SILENT
Cuffs
© VALLOX • We reserve the right to make changes without prior notification.
13
INSTALLATION
Cuffs
Ceiling mounting plate
Ceiling mounting plate
VALLOX 75/95 location
VALLOX 75 / 95 SILENT is mounted in a place where temperature is more than +10
°
C. The
unit must be located in a place where the acoustic disturbance for residents is minimal. If
residents can boost ventilation so that it exceeds the ratings for the time of operation, the
sound level rating may be exceeded by +10 dB. If needed, the unit shall be encased.
Ceiling mounting
VALLOX 75 / 95 Silent is mounted in place with an easy-to-use ceiling mounting plate (patent
pending). This prevents sounds of operation from passing through to the wall structures. The
ceiling mounting plate is fixed to the ceiling with M8 thread bars. Fix the bars so that they
stand the weight of the unit, i.e. approximately 52 kg.
The ceiling mounting plate has to be fixed
horizontally in order to ensure that the unit will be straight.
The outdoor air duct must be insulated against condensation, also between the unit and the ceiling mounting
plate. Special "cuffs" (4 pcs) are delivered with the unit for this purpose.
Installation
Lift the unit straight upwards till the locking wings on the sides of the mounting plate lock
into the side plates of the unit. You can detach the unit from the mounting plate by releasing
the locking wings from the side plates. To facilitate mounting, you may use a lubricant, such
as O-ring grease, in the collar seals. Mounting accessories comprised in the delivery include
rubber silencers, base plates and nuts as well
as insulated cuffs to be located between the unit
and the ceiling mounting plate. Thread bars are
not included in the delivery.
Ceiling mounting
10
53
– 0.0
+3.0
LOCKING WING
DET2
25
514
15
292
564
400
DET3
DET3
Back edge of the
ceiling mounting plate
VALLOX 95
back edge of
the side plate
DET3
4 x ø125
female
height
55
DET2
Lower edge
of the ceiling
mounting
plate
Upper edge of
the VALLOX
75-95 side
plate