The condensing water pipe must
have a downward slope.

The condensing water pipe must
never be connected directly to the
sewer.

It is not recommended to connect
a condensing water pipe to a water
seal or a floor drain where hot
wash or shower water goes.

(If hot wash water goes to the floor
drain and condensing water seal
gets dry during the summer,
steaming air is released from the
drain to the unit's negatively
pressured outlet side, which causes
water to condense from the air in
the pipe. A condensed water drop
may generate an audible sound
from the floor drain. The sound
may be generated in winter as well
if the water seal of the condensing
water pipe is not filled and does
not prevent air from flowing. Air
flow and the formation of water
drops in the condensing water pipe
should be prevented.)

The delivery does not include a
water seal nor the pipe and its
components.

Examples of condensing water connections

Yl

i 6

00

n. 

10

0

n. 

10

0

Suction air

C

O

LL

EC

TO

R,

 c

o

nd

en

si

ng

 w

a

te

g

o

es

 to

 th

ce

lla

r

Water seal at

the lower end

n. 

10

0

Suction air

and filling

Normally to the floor
drain

May generate sound when
the water seal gets dry.

When there is no condensing water, the
water seal may get dry in 1 to 4 weeks.

To the water seal in

the wash basin

May generate sound
when the water seal
gets dry.

Normally to the floor

drain with a long water

seal

A long water seal ensures
soundlessness for a long
time.

Straight to the floor

drain without a

water seal

The downward slope of
the pipe is so steep that
a water drop generating
sound cannot remain in
the pipe.

Normally to the floor

drain

The pipe has a fork which
decreases suction from the
floor drain. No sound. Water
seal not necessary. The fork
can also be used to fill the
water seal if such a seal is
used.

Normally to the floor

drain through a

funnel

No water seal. No sound
because there is no
suction in the pipe. The
unit sucks replacement
air from the funnel.

Normally to the floor

drain through a non-

return valve

The valve prevents air flow
in the pipe but lets
condensing water flow into
the floor drain. No sound.

To the collector

No sound. (Blocks of
flats)

Upper end sealed

Содержание 75 SILENT

Страница 1: ...changer efficiency approx 60 Summer winter damper Electric 500 W radiator or water radiator VKL G 3 F 7 G 3 52 kg Door switch Cooker hood PTX PTXP control centre 1992 1992 EK or remote monitoring cont...

Страница 2: ...welling 4 3 2 1 VALLOX 75 95 SILENT DIMENSIONS AND MAIN PARTS 2 2 Main parts Extract air fan Supply air fan Postheating radiator electric or water Heat recovery cell Outdoor air filter F7 1 2 3 5 4 6...

Страница 3: ...OX 75 95 SILENT Pressure loss in ducts Total pressure SFP Specific Fan Power guideline value 2 5 kw m3 s SFP Input power total W Air flow max dm3 s Pressure loss in ducts Total pressure SFP Specific F...

Страница 4: ...52 53 55 28 36 44 47 51 53 54 20 30 39 42 45 47 49 19 33 37 41 43 44 76 79 83 85 89 90 89 50 54 60 62 65 67 68 61 67 73 74 79 78 80 53 61 67 69 72 74 75 41 48 57 60 63 65 67 29 32 39 42 44 46 47 22 3...

Страница 5: ...summer position airflow through the cell is prevented and heat recovery bypass is activated REMOTE MONITORING CENTRE VALLOX 1993A ON OFF switch Operating status data to remote monitoring Transformer...

Страница 6: ...he flow of outdoor air to the unit The unit starts automatically as soon as the risk of freezing has passed The threshold temperature of the risk of freezing can be set at the thermostat J of the wate...

Страница 7: ...the front edge of the damper below the front edge of the collar When detaching the damper take the same steps in the opposite order Self actuated one way dampers are only used in VKL model units B C D...

Страница 8: ...of the electric radiator The overheat protector T2 of the radiator R is triggered and power supply to the heating unit is stopped if the temperature of the thermostat exceeds 80 C The overheat protect...

Страница 9: ...stops the unit when the temperature of water radiator goes below the threshold value preventing the risk of freezing in the water radiator This also causes self actuated one way dampers SP to close p...

Страница 10: ...1 L L N L 3 2 N INTERNAL ELECTRICAL CONNECTION OF THE HOODS N L VALLOX 95 75 COOKER HOOD PTXP A 27983 COOKER HOOD PTX 27983 HOOD Distribution panel L3 230 V 160 V 120 V 70 V L N 90 V 135 V 180 V 1 5...

Страница 11: ...internal electrical connection F1 Supply air fan F2 Extract air fan T1 Post heating radiator regulating thermostat 0 25 C Limitation T2 Defrost thermostat 5 C K Capacitor SS Safety switch Wire colour...

Страница 12: ...LENT 12 ELECTRICAL CONNECTIONS REMOTE MONITORING VALLOX 75 95 control through remote monitoring with control centre 1993 YK 2A VALLOX 1993A YK 2A VALLOX 75 95 REMOTE MONITORING CONTROL CENTRE DISTRIBU...

Страница 13: ...plate has to be fixed horizontally in order to ensure that the unit will be straight The outdoor air duct must be insulated against condensation also between the unit and the ceiling mounting plate S...

Страница 14: ...he pipe and its components Examples of condensing water connections Yli 600 n 100 n 100 Suction air COLLECTOR condensing water goes to the cellar Water seal at the lower end n 100 Suction air and fill...

Отзывы: