2.4. Ventilation control with carbon dioxide sensor (option)

•  In carbon dioxide control, VALLOX 180 SE adjusts fan speed so as to keep carbon

dioxide content in the ventilation zone below the setpoint. When two or more sensors
are used, fan speed is adjusted according to the highest measuring result.

•  It is possible to connect 1...5 carbon dioxide sensors as options to the VALLOX 180 SE

unit.

•  The adjustment is switched on / off and, if needed, the setpoint (500...2000 ppm) is set

at the control panel. The factory setting is 900 ppm. The recommended maximum
carbon dioxide content in good indoor air is 1,000 ppm.

•  When carbon dioxide control is on, the control panel may be used to raise fan speed to

the maximum fan speed and to decrease it to the basic fan speed. In carbon dioxide
control, maximum fan speed limitation is enabled.

2.5. Ventilation control with humidity sensor (option)

There are two methods for adjusting fan speed.
1

Automatic humidity setting

, which is suitable for controlling humidity in washing facilities, for

instance. The program records current humidity level and selects it as the setpoint, which
it then uses as the target for drying air in a bathroom e.g. after a shower. The setpoint
automatically varies according to season, for instance, and is always at the right level.
This setting is factory selected.

2 Humidity level can also be set 

fixed

. The setting can be set at the control panel, within the

range of 1...99 %RH. This can be used in public saunas and swimming pools, for
instance. The program aims at keeping humidity at the setpoint. The setpoint can be
changed if needed.

Adjusting mode is chosen at the controller. Recommended humidity content of good indoor
air is approximately 45%.
•  When this control is on, the control panel may be used to raise fan speed to the

maximum fan speed and to decrease it to the basic fan speed.

•  In humidity control, fan speed varies between the basic and maximum fan speeds

selected.

•  When the unit is first taken into use 

with automatic setpoint search enabled

 (factory setting), 

it

takes 3 to 10 hours for the program to define the value

. During this time, humidity adjustment is

not enabled (because the first value, selected at the factory, is 100%).

• Automatic search is enabled even if humidity control is not selected.

2.6. Ventilation control with voltage or current signal

VALLOX 180 SE fan power can be controlled with a voltage or current signal coming from
remote monitoring.
•  The signal can be used to select speeds 0–8. However, the set maximum fan speed

cannot be exceeded if carbon dioxide or humidity adjustment is active, or if maximum
fan speed limitation has been selected in the settings menu to be in operation all the time
(see the instructions for using the control panel in Section 3.3.6).

•  The signal changes the basic fan speed.
•  The signal does not lock fan speed, i.e. fan speed can be changed at the control panel

within the set limits. Carbon dioxide and humidity adjustment also operate within the set
limits.

2.7. Ventilation control with remote monitoring system (option)

•  With an optional LON converter, VALLOX 180 SE can be connected to the remote

monitoring system.

• When 

VALLOX 180 SE is connected to the remote monitoring system, compatibility

between the two needs to be ensured.

•  The remote monitoring system can control the same functions as the control panel does.
•  The remote monitoring system works in parallel with the control panel as well as carbon

dioxide and humidity sensors.

Carbon dioxide sensor (CO

2

)

Humidity sensor (RH)

LON converter

2.4.

2.5.

Содержание 180SE

Страница 1: ...TH LCD DISPLAY 1 09 283E 19 8 2008 Tyyppi 3486 VALLOX INSTRUCTIONS FOR USE AND MAINTENANCE Electronically controlled supply extract ventilation with heat recovery VALLOX We reserve the right to make changes without prior notification SE ...

Страница 2: ...esh Empty dwelling To save energy ventilation can be adjusted to the minimum level Cooking If the ventilation unit is connected to a coo ker hood boost ventilation during cooking The most common way to abate coo king fumes is to have a separate cooker hood 1 THREE QUESTIONS ABOUT VENTILATION 1 1 Why is air replaced in dwellings p 3 1 2 What are the characteristics of adequate ventilation p 3 1 3 H...

Страница 3: ...ated It is especially important for humidity and carbon dioxide content of indoor air to stay at a healthy level Recommended humidity content of good indoor air is approximately 45 Humidity content is lower in winter and higher in summer and autumn Dust mites thrive in indoor air if humidity exceeds 50 and if humidity stays at over 60 for a long time in winter water will condense in the cold struc...

Страница 4: ...temperature Furthermore demand controlled ventilation can be adjusted automatically with optional carbon dioxide and humidity sensors The fan power of the unit can also be controlled with a voltage or current signal 2 3 Ventilation control with control panel The control panel can be used for the following ventilation control functions Functions for adjusting ventilation power Starting and stopping...

Страница 5: ...ode is chosen at the controller Recommended humidity content of good indoor air is approximately 45 When this control is on the control panel may be used to raise fan speed to the maximum fan speed and to decrease it to the basic fan speed In humidity control fan speed varies between the basic and maximum fan speeds selected When the unit is first taken into use with automatic setpoint search enab...

Страница 6: ...upply air cascade control Supply air temperature control can be changed into cascade control It changes the controlling principle of the post heating radiator The temperature of air blown to the ventilation zone is controlled on the basis of extract air The program tries to keep supply air temperature at a value determined by the difference between extract air and the setpoint as follows If extrac...

Страница 7: ...ating unit option The antifreezing function aims at preventing a water circulating post heating unit from freezing The automatic function stops the supply and extract air fans as soon as outdoor air temperature falls below 0 C and supply air temperature below 7 C in which case also the control valve becomes wide open The control panel displays the fault message FREEZING ALERT irrespective of displ...

Страница 8: ... while after the functions stops Booster switch function The booster switch raises the fan speed to the set maximum speed for 45 minutes The function is started at the main display of the control panel by simultaneously pressing and holding down the and buttons for 2 seconds The function can also be started at a separate auto reset push button switch wired from the connection box of the unit to a ...

Страница 9: ...3 1 items 5 and 6 in the figure To settings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward 6 Scrolling down With this button you can scroll the displays downward 7 Increase button With this button you can increase values 8 Decrease button With this button you can decrease values 2 Carbon diox...

Страница 10: ...Factory settings see manual The adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval 10 The maintenance reminder is reset by pressing the and buttons simultaneously This turns out the maintenance reminder symbol in the main display 3 3 10 Resetting the service reminder Ma...

Страница 11: ...0 The desired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operating temperature of heat recovery cell bypass Cell bypass 10C The desired adjustment value for the DC fan is selected with the and buttons The rotation speed of the supply air fan can be lower...

Страница 12: ...an speed is lowered back to 4 Move the cursor with the arrow keys and change values with the and buttons Note that Exit and saving are done when the programming is finished by moving the cursor below the word Exit and pressing or Changes in fan speed Sp and supply air temperature Tmp are only made for the hours desired in other cases use N no change to previous Monday D 1 07 00 hours H 7 fan speed...

Страница 13: ...y Do not handle the filters with force When washing is done properly filters stand cleaning 3 to 4 times In other words you have to replace them at least every two years or when needed 4 2 Fans Check the cleanliness of the fans in connection with the maintenance of the filters and heat recovery cells If needed clean them Before cleaning remove the fans from the unit Removing of fans in AC model al...

Страница 14: ... external grille or by the closing of the supply air valves in the rooms If after checking these things the symbol continues to light up at small speeds adjust the setpoint greater 4 5 Condensing water During the heating season humidity of extract air condenses to water Water formation may be abundant in new buildings or if ventilation is low compared to the humidity build up caused by the residen...

Страница 15: ...s by 1 or 2 C It extends the period between stop ping and starting See the instructions for using the control panel Section 3 3 22 If the preheating radiator does not operate check if over heating protection prevents it from operating press the overheating protection reset button and measure the tempe rature of outdoor air inside the unit before the heat recovery cell when the door is closed If th...

Страница 16: ... a protecting plate the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube fuse If needed contact a maintenance company e g to check the glass tube fuse The unit does not obey the control panel 13 Remove or switch off the power supply fuse of the unit located in the distribution panel or the circuit breaker Wait for 30 seconds and p...

Отзывы: