4.5.2 Terminal Preparation

Gently clean the contact surface of the terminals with a brass bristle brush or a Scotch Brite pad. 

CAUTION! Use extreme care not to short the battery connections. VALEN Batteries are capable of 
very high short circuit currents. 

Before the final tightening of the connections, visually check that the connections are correct and in 
the required sequence. See section 4.5.4 for the procedure on checking string voltage. 

4.5.4 Voltage Checks

Visually check that all connections are properly made (positive to negative) and are tight. Measure 
module voltage, check that this is between 11.8V-13.8V. 

CAUTION! High voltage may be present. 

If the voltage of a module is not between these values, contact your VALEN representative for 
further instructions. 

4.5.5 Battery to Charger Connection

Ensure that the charger is disconnected from the power line. If a battery disconnect is installed, 
open it. 

NOTE! The positive terminal of the battery bank should be connected to the positive terminal of 
the charger and the negative terminal of the battery bank should be connected to the negative 
terminal of the charger. 

4.5.6 Paralleling of Batteries

When greater capacity is desired than available from a single cell or string, paralleling of batteries 
becomes necessary. Batteries must be properly paralleled to get the best system performance and 
longest battery life. The battery strings must be treated as equally as possible. This means equal 
length cabling to a common collection point from the load cables, uniform temperature between the 
strings and equal strings of batteries. Do not parallel other batteries with VALEN Batteries. To check 
the proper paralleling of the strings, connect the strings in the final form and place a load on the 
battery. Measure the load cable voltage drops. The voltage drops should match within 10%.

5.1 Charging the Valen ENLiFEN Batteries

The VALEN ENLiFEN batteries must be charged with a suitable battery charger or Solar Controller 
that has a lithium charging profile. Charging voltages and charge current should be limited to that of 
the BMS current rating,  which can be found on the batteries specification sheet. 

Section 5

 

Operation

7

INDUSTRIAL BATTERY & ENERGY STORAGE SOLUTION PROVIDER

AUS

  

1300 734 253     NZ  0800 734 253

Содержание ENLiFEN

Страница 1: ...valen com au www valen com au NEW ZEALAND 0800 734 253 sales valen co nz www valen co nz VALEN ENLiFEN LITHIUM INSTALLATION AND OPERATING INSTRUCTIONS VERSION 1 APRIL 2021 TO BE INSTALLED BY A SUITABL...

Страница 2: ...e storing and transporting the batteries 5 When on charge float voltages must be measured Be particularly careful because shorting a battery at this time can cause severe equipment failure and persona...

Страница 3: ...on delivery inspect the batteries for damage caused in transit Damaged pallets or packing material or disarrayed batteries could indicate rough improper handling in transit Describe in detail take pho...

Страница 4: ...re is 5 C to 30 C VALEN ENLiFEN LiFePO4 Batteries must be charged at least every 6 months while in storage If stored at ambient temperatures above 30 C charge the batteries every 4 months Storage of b...

Страница 5: ...gas during normal charging and discharging However ensure some air exchange is present in the ventilation 4 1 4 Floor Loading Whilst this is not quite as severe a problem as with VRLA batteries befor...

Страница 6: ...te 4 5 1 Cabling Recommendations Battery ratings are specified at the terminals of the battery The cabling used to connect the battery terminals to the load has a voltage drop when the battery is disc...

Страница 7: ...e terminal of the battery bank should be connected to the negative terminal of the charger 4 5 6 Paralleling of Batteries When greater capacity is desired than available from a single cell or string p...

Страница 8: ...dust accumulations If required a solution of 1kg of baking soda in 4L of water may be used as a multipurpose cleaner if more stubborn stains or dirt accumulations are present Follow the rack or cabin...

Страница 9: ...attery and determining the actual time the battery will support the load This test is done in the case of a UPS by switching into a test mode where the battery becomes the primary source and the norma...

Страница 10: ...TRALIA 1300 734 253 sales valen com au www valen com au NEW ZEALAND 0800 734 253 sales valen co nz www valen co nz Company Details Legal Entity Valen Power Pty Ltd ACN 134 028 961 Telephone 1300 734 2...

Отзывы: