background image

7.1 General

Discharge testing of the battery is performed to determine the battery capacity. There are two 
reasons for performing this test: 

1.  A rating test discharge – the intention here is to determine the percent of battery capacity as 

compared to the rated capacity. This is typically an 8hour discharge test. 

2.  A service test discharge – this test is to determine the battery standby time under the actual 

load conditions of intended battery usage. The rating test discharge is usually performed 
using a suitably designed and sized load bank to provide a constant DC current load to the 
battery. The test is performed for the specified period of time to an end-point voltage per 
cell with the ampere-hour capacity of the battery calculated by multiplying the number 
of hours of run time. The actual Ah capacity can be compared to the rated Ah capacity to 
determine percentage capacity. This type of test is usually used as an acceptance test of the 
battery. The service test is usually performed by placing the actual load on the battery and 
determining the actual time the battery will support the load. This test is done, in the case 
of a UPS, by switching into a test mode where the battery becomes the primary source and 
the normal AC line becomes the backup. If the load is not critical, the AC input can simply be 
shut off to simulate a loss of power event and total system operation can be verified as well. 
A load bank can be used if the normal battery load is well defined. 

 

7.2 Test Procedure

 

The battery test procedure for either test is: 

1.  Ensure the battery is fully charged before capacity testing and that all connections are clean and 

tight. If the battery has not been on charge for at least one week, re-attach the charger, then do 
the test after a week of the battery being on charge. 

2.  Prepare the load bank or test the load system. Ensure all temporary cable connections are 

secure and connected to the proper polarity, and have sufficient current-carrying capacity.

3.  Determine the battery temperature by measuring and recording the temperature of every 15 

blocs.  

 For further technical support, please contact VALEN on the below details.  

Section 7 

Capacity Testing

9

INDUSTRIAL BATTERY & ENERGY STORAGE SOLUTION PROVIDER

AUS

  

1300 734 253     NZ  0800 734 253

Содержание ENLiFEN

Страница 1: ...valen com au www valen com au NEW ZEALAND 0800 734 253 sales valen co nz www valen co nz VALEN ENLiFEN LITHIUM INSTALLATION AND OPERATING INSTRUCTIONS VERSION 1 APRIL 2021 TO BE INSTALLED BY A SUITABL...

Страница 2: ...e storing and transporting the batteries 5 When on charge float voltages must be measured Be particularly careful because shorting a battery at this time can cause severe equipment failure and persona...

Страница 3: ...on delivery inspect the batteries for damage caused in transit Damaged pallets or packing material or disarrayed batteries could indicate rough improper handling in transit Describe in detail take pho...

Страница 4: ...re is 5 C to 30 C VALEN ENLiFEN LiFePO4 Batteries must be charged at least every 6 months while in storage If stored at ambient temperatures above 30 C charge the batteries every 4 months Storage of b...

Страница 5: ...gas during normal charging and discharging However ensure some air exchange is present in the ventilation 4 1 4 Floor Loading Whilst this is not quite as severe a problem as with VRLA batteries befor...

Страница 6: ...te 4 5 1 Cabling Recommendations Battery ratings are specified at the terminals of the battery The cabling used to connect the battery terminals to the load has a voltage drop when the battery is disc...

Страница 7: ...e terminal of the battery bank should be connected to the negative terminal of the charger 4 5 6 Paralleling of Batteries When greater capacity is desired than available from a single cell or string p...

Страница 8: ...dust accumulations If required a solution of 1kg of baking soda in 4L of water may be used as a multipurpose cleaner if more stubborn stains or dirt accumulations are present Follow the rack or cabin...

Страница 9: ...attery and determining the actual time the battery will support the load This test is done in the case of a UPS by switching into a test mode where the battery becomes the primary source and the norma...

Страница 10: ...TRALIA 1300 734 253 sales valen com au www valen com au NEW ZEALAND 0800 734 253 sales valen co nz www valen co nz Company Details Legal Entity Valen Power Pty Ltd ACN 134 028 961 Telephone 1300 734 2...

Отзывы: