Installation Manual - L48
ENGLISH
Installation rules and advice
• The minimum height of the hot air duct is 32 ¼" (819 mm). It must be measured from the fireplace
opening to the bottom of the hot air outlets.
• Do not connect the hot air ducts to a central heating system. The malfunction of the heating system
would overheat the fireplace.
• Do not use insulated ducts as they may overheat.
• Do not use «T» fittings or anything other than those listed below.
• Hot air outlets must be installed in the same room as the fireplace.
Do not install either outlet in
adjoining or upstairs rooms.
• When forced air kit is installed in conjunction with a gravity kit, the forced air device will draw some of
the air from the gravity kit ducting, therefore reducing its efficiency.
Clearances
• There must be a clearance of at least 6" (152 mm) between the frame of the hot air outlet and a ceiling.
There must be a clearance of at least 6" (152 mm) between the frame of the hot air outlet and a side
partition or a mantle made of combustible material.
6"
149mm
MIN.
NON COMBUSTIBLE
MATERIAL AREA
6"
MIN.
32 1/4"
MIN.
COMBUSTIBLE
MATERIAL
FRAMING HEADER
NON-COMBUSTIBLE