Appendix A. Modbus Reference
A.1 Default Communication Settings
The following table lists the default Modbus serial settings of devices ordered with the Modbus
configuration option.
Table 49 Default Modbus Serial Communication Settings
Description
Default Value
Serial bit rate
19200
Parity
N
Number of data bits
8
Number of stop bits
2
Modbus device address
240
Serial delay
0
Communication mode
Modbus RTU
A.2 Function Codes
Table 50 Modbus Function Codes
Function Code (Decimal)
Function Code (Hexadecimal)
Name
03
03
hex
Read Holding Registers
16
10
hex
Write Multiple Registers
43/14
2B
hex
/ 0E
hex
Read Device Identification
A.3 Data Encoding
Registers using "32-bit float" data format are encoded using the "binary32" encoding defined
in IEEE 754 (also known as "single-precision floating point format").
The least significant 16 bits of a floating point number are placed at the Modbus register listed
in the table, while the most significant 16 bits are placed in the register with number/
a 1, as specified in Open Modbus TCP Specification, Release 1.0. This is also known as
"little-endian" or "Modicon" word order.
HMDW110 User Guide
M211726EN-D
78
Содержание hmdw110 series
Страница 1: ...M211726EN D User Guide Vaisala Humidity and Temperature Transmitter Series HMDW110 ...
Страница 5: ...Recycling 87 Table of Contents 3 ...
Страница 14: ...2 5 HMS110 112 Parts 1 2 3 4 5 6 7 8 9 10 11 Figure 3 HMS110 112 Parts HMDW110 User Guide M211726EN D 12 ...
Страница 25: ...3 Mount the transmitter using two screws of sufficient length 100 mm Ø 5 5 mm Chapter 3 Installation 23 ...
Страница 87: ...Appendix A Modbus Reference 85 ...
Страница 88: ...HMDW110 User Guide M211726EN D 86 ...
Страница 90: ...HMDW110 User Guide M211726EN D 88 ...
Страница 91: ......
Страница 92: ...www vaisala com ...