4. Modbus Communication
Transmitters ordered with the Modbus configuration option are accessed using the Modbus
serial communication protocol. The supported Modbus variant is Modbus RTU (Serial Modbus)
over RS-485 interface.
The supported Modbus functions and registers are described in
The following table lists the default Modbus serial settings of devices ordered with the Modbus
configuration option.
Table 4 Default Modbus Serial Communication Settings
Description
Default Value
Serial bit rate
19200
Parity
N
Number of data bits
8
Number of stop bits
2
Modbus device address
240
Serial delay
0
Communication mode
Modbus RTU
Use Vaisala Insight software to change the Modbus serial communication settings if needed.
More Information
‣
Vaisala Insight Software (page 29)
HMDW110 User Guide
M211726EN-D
28