Code
Meaning
Cause
Remedy
F.741
Building circuit: Return temp. too
low
–
During the de-icing, the return tem-
perature falls below 13 °C
–
Ensure the minimum installation
volume is maintained; if required,
install a series return cylinder
–
The fault message is displayed until
the return temperature increases to
above 20 °C.
–
Activate the electric back-up heater
in the product's control panel and
in the system control in order to
increase the return temperature. The
compressor is blocked while the fault
message is present.
F.752
Fault: Frequency converter
–
Internal electronics fault on the in-
verter PCB
–
Mains voltage outside of 70 V
–
282 V
–
Check the integrity of the power sup-
ply cables and compressor connec-
tion cables
The plugs must audibly click into
place.
–
Check the cable
–
Check the mains voltage
The mains voltage must be between
195 V and 253 V.
–
Check the phases
–
Replace the frequency converter, if
required
F.753
Connection fault: Freq. conv.
n.recogn.
–
Missing communication between the
frequency converter and the outdoor
unit's control PCB
–
Check the integrity of the wiring
harness and plug connection and,
if required, replace them
–
Check the frequency converter by
actuating the compressor safety
relay
–
Read the assigned parameters for
the frequency converter and check
whether values are displayed
F.755
Fault: 4-port valve position not
correct
–
Incorrect position of the 4-port di-
verter valve. If, in heating mode, the
flow temperature is lower than the
return temperature in the building cir-
cuit.
–
The temperature sensor in the EEV
environment circuit displays an incor-
rect temperature.
–
Check the 4-port diverter valve (is an
audible switching available? Use the
sensor/actuator test)
–
Check that the coil is positioned
correctly on the 4-port valve
–
Check the wiring harness and plug
connections
–
Check the temperature sensor in the
EEV environment circuit
F.774
Sensor fault: Air inlet temp.
–
The sensor is not connected or the
sensor input has short-circuited
–
Check and, if required, replace the
sensor
–
Replace the wiring harness
F.785
Fan unit 2: Fan blocked
–
There is no confirmation signal stat-
ing that the fan is rotating
–
Check the air route and, if required,
remove any blockages
F.788
Building circuit: Pump fault
–
The electronics system of the high-
efficiency pump has detected a
fault (e.g. dry running, blockage,
overvoltage, undervoltage) and has
switched off and locked the pump.
–
Switch the heat pump off for at least
30 seconds (no current)
–
Check the quality of the plug contact
on the PCB
–
Check that the pump functions cor-
rectly
–
Purging the building circuit
–
Check that the dirt filter that is in
place is permeable
F.817
Freq. converter fault: Compressor
–
Defect in the compressor (e.g. short
circuit)
–
Defect in the frequency converter
–
Connection cable to the compressor
is defective or loose
–
Measure the winding resistance in
the compressor
–
Measure the frequency converter
output between the three phases, (it
must be > 1 k
Ω
)
–
Check the wiring harness and plug
connections
F.818
Freq. converter fault: Mains
voltage
–
Incorrect mains voltage for operating
the frequency converter
–
Shutdown via the energy supply
company
–
Measure and, if required, correct the
mains voltage
The mains voltage must be between
195 V and 253 V.