*****INTERNAL*****30 R_D proof- 26.10.2022 / 09:15:46- VaillantGroup\DOC-agt\Brand\VIH_QW_190_6\ENG\OI-II_GB_0020291525
40
Installation and maintenance instructions 0020291525_04
▶
Activate the internal electric back-up heater with one of
the output levels.
▶
You can find the output levels for the electric back-up
heater in the tables in the appendix.
5.4 kW back-up heater at 230 V and at 400 V
(
▶
Ensure that the maximum output for the electric back-up
heater does not exceed the output of the fuse protection
for the household electricity system .
8.10
Setting the anti-legionella function
▶
Set the anti-legionella function using the system control.
To ensure sufficient anti-legionella protection, the electric
back-up heater must be activated.
Condition
: Internal electric back-up heater deactivated or external back-up
heater
The anti-legionella function can be used without a back-up
heater in the outdoor temperature range of -10 °C to +30 °C;
outside of this temperature range, the function can only be
used with an activated internal or external back-up heater.
An external back-up heater must be protected against over-
heating, for example, so that it is intrinsically safe. An ex-
ternal back-up heater must be connected to contact
X14
via
a cut-off relay. On the indoor unit's control, the setting must
be converted to the external back-up heater under
MO relay
.
Menu
→
Installer level
→
Configuration
.
8.11
Calling up the installer level
1.
Press
and
at the same time.
2.
Navigate to
Menu
→
Installer level
and confirm by
pressing
(
OK
).
3.
Set the value
17
and confirm by pressing
.
8.12
Checking the configuration
You can recheck and set the most important system para-
meters. Call up
Configuration
to configure the menu item.
Menu
→
Installer level
→
Configuration
.
8.13
Calling up statistics
Menu
→
Installer level
→
Test menu
→
Statistics
You can use this function to call up the statistics for the heat
pump.
8.14
Displaying the filling pressure in the building
circuit
The product has a pressure sensor in the heating circuit and
a digital pressure display.
▶
Select
Menu Live Monitor
to display the filling pressure
in the building circuit.
8.15
Activating cooling mode
▶
Go to the indoor unit's control panel.
▶
Navigate to:
Menu
→
Installer level
→
Configuration
→
Cooling technology
.
▶
Select: Active cooling.
▶
If this involves a heat pump cascade, implement this set-
ting for every heat pump with cooling function.
Condition
: System control present
▶
Go to the system control.
▶
Activate cooling mode (
→
Instructions for the system con-
trol).
8.16
Checking function and leak-tightness
Before you hand the product over to the end user:
▶
Check the heating installation (heat generator and sys-
tem) and the domestic hot water pipes for tightness.
▶
Check whether the drain pipework for the purging con-
nections has been installed correctly.
8.16.1 Checking the heating mode
▶
Start check programme P.04.
8.16.2 Checking the domestic hot water generation
▶
Check whether the cylinder is purged and the domestic
hot water temperature is reached.
8.17
Floor drying
–
Condition: No system control connected
Caution.
Risk of damage to the product caused by
impermissible purging
Without purging the heating circuit, the sys-
tem may become damaged.
▶
If the screed drying is activated without a
system control, purge the system manu-
ally. No automatic purging takes place.
–
You can use this function to "dry heat" freshly laid screed
in accordance with the construction regulations, accord-
ing to a defined time and temperature schedule, without
the need for a system control to be connected.
VIH QW 190/6
If there is no electric back-up heater, screed drying is
only possible with this product if the return temperature is
above 10 °C. This corresponds approximately to an outdoor
temperature of +5 °C. At outdoor temperatures below
+5 °C, there is a risk of increased icing of the fin-type heat
exchanger in the outdoor unit.
When screed drying is activated, all the selected operating
modes are interrupted. The function controls the flow tem-
perature of the controlled heating circuit according to a pre-
set programme, regardless of the outdoor temperature.
The display shows the target flow temperature. You can
manually set the current day.