background image

Instructions for use 3

uniSTOR GB

7

3.5 Important notes

Shutting down the uniSTOR cylinder

To shut down the heating and hot water system for
short periods, simply turn off the boiler as shown in the
instructions supplied with the boiler.

Frost protection

Please ensure that if you are absent during a period of
frost the central heating system remains in operation
and the rooms and uniSTOR cylinder are kept above
freezing point.

Alternatively you can drain the central heating system,
boiler and uniSTOR cylinder. Please contact your
Installer.

Care and Maintenance

The casing of the uniSTOR cylinder may be cleaned with
a damp cloth and a little soap. Do not use any abrasive
or solvent material which could damage the case or
fittings.
It is important that your hot water cylinder is serviced
annually by a competent person. Please contact your
installer or Group Service (0870 - 6060777) for further
details.

3.6 Guarantee

Vaillant offers a guarantee of 25 years for the stainless
steel vessel against faulty materials or manufacture.
The following information is important as without it your
guarantee may be invalid.
1.

The warranty will become invalid if the damage is
due to frost or freezing, transient voltages, lightning
strikes or any act of vandalism or misuse

2. The proof of purchase must be produced in the event

of any warranty claim (bill of sale)

3. The uniSTOR must be installed by a competent

person to the prevailing standards, installation book
and building regulations at the time of installation

4. The Benchmark Cylinder Commissioning Checklist

must be completed on installation and kept up to
date

5. The uniSTOR must be serviced annually
6. The installation must be in an appropriate location

and its use is restricted to potable water (chloride
levels less than 200 mg/l)

7. Tampering or modification will invalidate the

warranty

8. The guarantee card must be completed and returned

to Vaillant Ltd. within 30 days of purchase

9. This guarantee does not cover the effects of scale.

For all other Vaillant parts (electrical, thermal controls,
valves and design elements) Vaillant carry a 2 year
guarantee.

3.4 Immersion heater

The electric immersion heater behind the front panel is
provided as a back up means of water heating and is not
intended for use at the same time that the boiler is
heating the cylinder.

Fig. 1a

1

Immersion heater 

2

Switch (Immersion heater ON/OFF)

3

Additional immersion heater for uniSTOR 260 and 310
(as accessory)

ON/OFF

1

2

3

0020005468_02_GB_042008.qxd  16.04.2008  14:17 Uhr  Seite 7

Содержание uniSTOR VIH GB SERIES

Страница 1: ...Instructions for Installation and Use uniSTOR Unvented hot water storage cylinder VIH GB 125 S VIH GB 155 S VIH GB 180 S VIH GB 210 S VIH GB 260 S VIH GB 310 S GB...

Страница 2: ...y System 8 4 2 Secondary Return 8 5 Installation 9 5 1 Installation requirements 9 5 1 1 Siting 9 5 1 2 Mains Water Pressure 9 5 1 3 Pipework Primary Circuit 9 5 1 4 Discharge Pipework 9 5 1 4 1 High...

Страница 3: ...ting is controlled by a separatly fitted 2 port valve in conjunction with suitable external controls such as a programmer room thermostat or thermostatic radiator valves 1 3 Immersion Heater uniSTOR c...

Страница 4: ...28 30 33 39 44 49 kg Weight full 145 175 205 245 310 340 kg Height 969 1179 1339 1499 1789 2109 mm Cylinder connections Cold mains inlet 22 mm compression DHW outlet 22 mm compression Balanced pressu...

Страница 5: ...ate cylinder heat up time 15 C to 65 C minutes Reheat time for 70 of cylinder contents minutes 50 40 10 20 30 40 60 50 30 20 12 Heat input to cylinder kW Cylinder Heat Up Times 15 20 25 30 38 35 VIH G...

Страница 6: ...d be completed by the installer and or commissioning engineer and handed to the user All CORGI registered installers carry a CORGI ID card and have a registration number Both should be recorded in you...

Страница 7: ...y will become invalid if the damage is due to frost or freezing transient voltages lightning strikes or any act of vandalism or misuse 2 The proof of purchase must be produced in the event of any warr...

Страница 8: ...aws of the local Water Undertaking The installation is subject to Building Regulation approval notify the Local Authority of intention to install In the event of parts replacement use only genuine spa...

Страница 9: ...uniSTOR unvented storage cylinder should not be installed Contact Vaillant Ltd for details on alternative hot water supply systems In order to minimise frictional losses minimum 22 mm bore is recomme...

Страница 10: ...g temperature relief valve 500 mm maximum 300 mm minimum providing that where children may play or otherwise come into contact with discharges a wire cage or similar guard is positioned to prevent co...

Страница 11: ...84 314 589 903 VIH GB 180 S 1308 1339 454 384 314 589 1038 VIH GB 210 S 1468 1499 454 384 314 589 1118 VIH GB 260 S 1758 1789 454 384 314 589 1408 1376 VIH GB 310 S 2078 2109 454 384 314 589 1648 1376...

Страница 12: ...niSTOR GB 12 1 Boiler 2 uniSTOR cylinder 3 2 port motorised valve provided with the boiler 4 Immersion heater 5 2 port motorised valve A Boiler flow B Boiler return Fig 5 1 A B 2 4 3 5 M M DHW 5 3 Fun...

Страница 13: ...f valve 2 Expansion relief valve 3 Pressure limiting valve combined with strainer 4 Connection to expansion vessel 5 Balanced pressure cold water outlet 6 Cold water mains inlet 7 DHW outlet 8 Tundish...

Страница 14: ...ns supply to the uniSTOR To ensure optimum performance from the uniSTOR and particularly in installations where the balanced pressure cold water outlet 5 fig 8 is to be used the pipework provided from...

Страница 15: ...pe runs are of excessive length or there are several terminal fittings supplied extend the length of pipework in 22 mm Connect the secondary return if required as shown in 4 2 Secondary Return 5 4 3 S...

Страница 16: ...ls 1 Thermostat adjustable b Immersion heater 2 Thermal cut out with Reset button 3 Sensor 2 1 2 a b 1 3 230 V AC 3 kW 1 2 3 N L Important The immersion heater incorporates an energy cut off device an...

Страница 17: ...for electrical installations IEE Wiring Regulations 16th edition Check that the sensors from the immersion heater and the cylinder are positioned correctly in the tubes Note A special accessory is off...

Страница 18: ...Note Earth not required Link L 2 5 Siemens Landis Staefa RWB2 RWB9 Potterton Myson EP 2002 EP 3002 EP 6002 Note Link L 5 Sunvic Select 207 N L 2 3 4 5 3 7 6 1 E N L 2 3 4 1 E N L 2 3 4 5 3 7 6 1 N 3 5...

Страница 19: ...4 5 6 7 8 9 10 SL 1 2 3 uniSTOR VIH GB Central Heating 2 Port Motorised Valve Hot Water 2 Port Motorised Valve Cylinder Stat E BL BR GR OR L N Pump E BL BR GR OR L N HW ON CH ON 2 Channel Programmer...

Страница 20: ...cylinder has reached temperature and all radiators in the system are hot Then once again drain the complete CH system to remove residues from the pipework and refill and vent again as above Reset the...

Страница 21: ...ring frost conditions Advise the user that the immersion heater is provided as a back up means of water heating and is not intended for use at the same time that the boiler is heating the cylinder Fin...

Страница 22: ...g to controls instructions Is 2 port valve in correct position DHW position Does cylinder thermostat operate Replace cylinder thermostat Vent heating coil of air H fig 4 Check replace 2 port valve Is...

Страница 23: ...ansion vessel Does pressure hold Turn off boiler and immersion heater Is discharge still occuring YES NOT OK Is the discharge occuring only when the cylinder is being heated YES NO Is pressure downstr...

Страница 24: ...ty YES Replace TPRV Replace immersion heater NO YES NO Is operation now OK OK Fault remedied NOT OK Check temperature control of boiler Does 2 port valve change to heating position when cylinder reach...

Страница 25: ...limiting valve OK Check pressure limiting valve OK Check sytem for blockage OK Symptoms still persisting YES Check system as for discharge from temperature or expansion relief valve Inform customer t...

Страница 26: ......

Страница 27: ......

Страница 28: ...0020005468_02 GB 042008 Subject to alteration Printed in Germany...