116
Parameter
Select/Display
Factory setting Suggested Setting
Remark
Anti-legio. time
00:00 – 23:59
04:00
Select a relevant time
We would normally suggest selecting
a time at the end of a DHW time
block so the DHW can be utillised for
the next DHW time frame. Usually
better timing during the day so there
are higher ambient temperature so
the heat pump can raise cylinder
temp most of the way without
needing to use back up heater.
Cylinder charging
hysteresis
3 – 20 K
5.0 K
5K
Cylinder charging
offset
0 – 40 K
25 K
8-10K dependant on
heat pump size
5-8kw = 8k
11-15kw =10k
Only with domestic hot water control
via VRC 720
Max. cyl. charging
time
- Off
- 20 – 120 min.
60 min.
See below table
Cyl. charg. anti-cycl.
time
0 – 120 min.
60 min.
5 mins
Parallel cyl.
charging
- No
- Yes
No
No
Domestic hot water temperatures are set in Control – Domestic hot water – domestic hot water temperatures:
recommendation 50-55°C
Heating Curve Graph
Cylinder charging times 10°C - 50°C
As a guide only, to ensure the heat pump can re-heat the cylinder is one cycle so heating is not compromised. Times may
need to be shortened if heat loss is high for the property so heating performance is not compromised. Maximum is 120
mins for this parameter.
aroTHERM plus KW output
3.5
5
7
10
12
Litres
150
110
74
55
37
29
200
120
98
74
49
39
250
120
120
92
61
49
300
120
120
110
74
59