7

Installation instructions Mixer module VR 60 0020020171_02

5.3 

Setting the Bus address

Communication within the system takes place via an 
eBus. To ensure flawless communication between all the 
components it is necessary to allocate a unique address 
to the individual mixer circuit. To do this set the value 4, 
6, 8, 10, 12 or 14 on the address switch (Fig. 5.3 (

3

)) de-

pending upon whether the VR 60 mixer module has al-
ready been integrated in the system.
Addresses 0 to 3 are used by the system circuits in the 
auroMATIC 620 and VRC 630 controllers or the Vaillant 
geoTHERM VW.. .../2 heat pump and are not therefore 
available for addressing.

Addresses to be 
set

Assignment in the auroMATIC 620/
VRC 630

Heating circuit a

Heating circuit b

4

HK 4

HK 5

6

HK 6

HK 7

8

HK 8

HK 9

10

HK 10

HK 11

12

HK 12

HK 13

14

HK 14

HK 15

Table 5.1  Bus addresses to be set

 AF  0

AF

2   1

VFb

3

Fig. 5.3  Setting the bus address

After connecting the electrical installation:
•  Fix all cables with the accompanying cable clamps 

(Fig. 4.2 (

2

)).

•  Insert the casing cover back into the hinges and hinge 

the casing cover back up into position.

•  Screw the casing cover in position in accordance with 

Fig. 4.1.

6 Start-up

Starting up the VR 60 mixer module is carried out in 
conjunction with starting up the auroMATIC 620 or 
VRC 630 controller or the Vaillant geoTHERM VW.. .../2 
heat pump. To do this, proceed in accordance with the 
instructions in the manual for the 
auroMATIC 620 or VRC 630 controller or the Vaillant 
geoTHERM VW.. .../2 heat pump.

7 Technical 

data

Unit

VR 60

Operating voltage

Power consumption

Contact load of the output relays (max.)

Maximum total current

V

VA

A

A

230

2

2

4

Maximum permissible ambient temperature

°C

40

Operating voltage sensor

V

5

Minimum cross-section of the sensor cables, 

eBUS cables

Minimum cross-section of power cable 

(rigid cable, NYM)

mm2

mm

2

0.75

1.5

Dimensions of wall mounting base

Height

Width

Depth

mm

mm

mm

174

272

52

Level of protection

Protection rating for regulator

IP 20

II

Table 7.1  Technical data

Electrical installation 5

Start-up 6

Technical data 7

Содержание Mixer module VR 60

Страница 1: ...For the heating engineer Installation instructions Mixer module VR 60 Bus module control system VR 60 GB For the heating engineer Installation instructions Mixer module VR 60 Bus module control system ...

Страница 2: ...stallation manu als of the various components of the plant when install ing commissioning and starting up Storage of the documents Pass on this installation manual to the owner of the sys tem in order for him her to store it so that it is available whenever it is required Symbols used Please observe the safety instructions in this installation manual for the installation of the appliance The symbo...

Страница 3: ...ting installa tions with integrated hot water generation The VR 60 mixer module can also be used as a system component with the Vaillant geoTHERM VW 2 heat pumps for controlling hot water central heating installations Any other use or extended use is considered to be improper The manufacturer or supplier is not liable for any result ing damage The owner alone bears the risk Intended use includes t...

Страница 4: ... ciated heating circuit time programme heating curve etc and to select the special functions party etc In addition it is possible to call up the displays of heating circuit and maintenance and faults on the boiler Com munication with the heating control unit is via the eBus VR 80 remote control device The VR 80 is a remote control unit for controlling a heating circuit within a control system with...

Страница 5: ...f sufficient to ensure that all the terminals on the system are voltage free If the casing of the VR 60 mixer module is closed open it as described in Chapter 4 3 5 1 Connecting the mixer module to the building Wire up the VR 60 mixer module as shown in Fig 5 1 Use the supplied eBus connection cable to incorporate the mixer module VR 60 in the communication sys tem The eBUS can be branched at any ...

Страница 6: ... a cylinder charging circuit not with Vaillant geoTHERM VW 2 heat pump You can also configure the heating circuits of the mixer module VR 60 as storage tank charging circuits addi tional hot water circuits Wire up the VR 60 mixer module as shown in Fig 5 2 230 V PE N L PE N L PE N L PE N Auf Zu PE N L AF 0 230 V HKa HKa P HKb P AF PE N Auf Zu HKb 2 1 VFb BUS 2 1 VFa 2 1 3 Fig 5 2 Connection of a h...

Страница 7: ...trical installation Fix all cables with the accompanying cable clamps Fig 4 2 2 Insert the casing cover back into the hinges and hinge the casing cover back up into position Screw the casing cover in position in accordance with Fig 4 1 6 Start up Starting up the VR 60 mixer module is carried out in conjunction with starting up the auroMATIC 620 or VRC 630 controller or the Vaillant geoTHERM VW 2 h...

Страница 8: ...structions The system owner will be granted a warranty in accordance with the Vaillant terms and conditions All requests for work dur ing the guarantee period must be made to Vaillant Service Solutions 0870 6060 777 8 2 Vaillant service To ensure regular servicing it is strongly recommended that arrangements are made for a Maintenance Agreement Please contact Vaillant Service Solutions 0870 6060 7...

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ...0020020171_02 GB 052009 Subject to alterations ...

Отзывы: