Operating Manual geoTHERM exclusive VWS 0020071929_00
30
Description
Unit
VWS 63/2 230 V
VWS 83/2 230 V
VWS 103/2 230 V
Integrated domestic hot water cylinder
- Contents
- Max. operating pressure
- Max. temperature with heat pump
- Max. temp. with heat pump and
auxiliary heating
l
MPa (bar)
°C
°C
175
1 (10)
55
75
Heat source circuit (brine circuit)
- Brine type
- Max. operating pressure
- Min. inlet temperature
- Max. inlet temperature
-
MPa (bar)
°C
°C
Ethylene glycol 30 %
0.3 (3)
-10
20
- Nominal flow rate dT 3K
- Residual head dT 3K
- Nominal flow rate dT 4K
- Residual head dT 4K
- Electrical power consumption - pump
l/h
mbar
l/h
mbar
W
1453
335
1090
433
132
1936
277
1452
397
132
2530
216
1898
398
195
CH circuit
- Max. operating pressure
- Min. flow temperature
- Max. flow temperature
MPa (bar)
°C
°C
0.3 (3)
25
62
- Nominal flow rate dT 5K
- Residual head dT 5K
- Nominal flow rate dT 10K
- Residual head dT 10K
- Electrical power consumption - pump
l/h
mbar
l/h
mbar
W
1061
386
517
490
93
1375
324
697
460
93
1803
399
848
580
132
Refrigerant Circuit
- Coolant type
-
R 407 C
- Quantity
- Number of revolutions EX valve
kg
-
1.9
9.0
2.2
9.0
2.05
9.0
- Permissible operating overpressure
- Compressor type
- Oil
- Oil filling quantity
MPa (bar)
-
-
l
2.9 (29)
Scroll
Ester
1.3
1,45
1,45
DHW circuit
Expansion vessel
bar
4
4
4
Expansion valve setting
bar
6
6
6
Maximum water supply pressure
bar
10
10
10
Pressure reducing valve
bar
3.5
3.5
3.5
Temperature and pressure relief valve
setting
ba r
7
7
7
ºC
95
95
95
Heat up time
min
113
98
86
Recovery time
min
88
74
60
Heat pump performance data
B0W35 dT5
- Heating output
- Power consumption
- Performance figure/COP
B5W55
- Heating output
- Power consumption
- Performance figure/COP
kW
kW
-
kW
kW
-
6.0
1.4
4.2
6.3
2.1
3.0
8,1
1.9
4.2
8.6
2.8
3.0
10.5
2.5
4.2
10.8
3.5
3.1
Maximum passive cooling output
under the following conditions: heating
flow VL = 18 °C and
heating return RL = 22 °C!
kW
3.8
5.0
6.2
Sound output
dbA
48
49
50
Conforms to safety regulations
-
CE mark
Low Voltage Directive 73/23/EWG
EMC Directive 89/336/EWG
EN 60335
ISO 5149
Table 7.1 Technical data (cont.)
7 Appendix
Содержание geoTHERM exclusive