Operating Manual geoTHERM exclusive VWS 0020071929_00
20
Display shown
Description
Factory setting
DHW loading
4
Parameters
Operating mode WW
Auto
Auto
Max. DHW temp.
60°C
60°C
Min. DHW temp.
44°C
44°C
Cylinder temp. REAL
51°C
51°C
>Select set target temperature
For connected domestic hot water cylinders and the
circulation circuit the operating modes Auto, On and
Off are possible.
The
maximum WW temperature
determines the
temperature to which the domestic hot water cylin-
der should be heated.
The
minimum WW temperature
determines the
limit below which the domestic hot water cylinder is
heated.
Note:
The maximum WW temperature is only dis-
played when the auxiliary hot water heating is ena-
bled.
Without electric auxiliary heating, the WW tempera-
ture is limited by the pressure sensor control shut-
off in the cooling circuit and cannot be adjusted!
Cylinder temp. REAL
: Current temperature in the
domestic hot water cylinder.
We recommend that hot water generation be
achieved without the electric auxiliary heating. by
this method, the maximum WW temperature is de-
termined by the high pressure cut-out in the heat
pump cooling circuit. This cut-out corresponds to a
maximum hot water temperature of 58 °C. In order
to keep the heat pump starts to an absolute mini-
mum as low a min. hot water temperature as possi-
ble should be selected.
Min. hot water
temp. 44 °C
HK2
5
Time programme
>Mon
1
00:00
24:00
2
:
:
3
:
:
>Select weekday/Block
You can set the heating times for each heating cir-
cuit in the
HK2-Timer programme
menu.
Up to three heating times can be programmed per
day or block. The control system operates according
to the heating curve and the room setpoint tempera-
ture.
The set back times can be dispensed with, depending
on the tariff agreement with power company (VNB)
or the construction of the house.
Power companies offer their own discounted tariffs
for heat pumps. It can make sense on economic
grounds to make use of the more favourable off-
peak power.
In low-energy houses (in Germany standard as from
1st February 2002 energy conservation regulation)
the room temperature reduction can be dispensed
with owing to low heat losses.
The desired set-back temperature must be set in
menu 2.
Mo. – Su.
0:00 – 24:00 hours
Table 5.1 Adjustable parameters at the operator level (contd.)