62
Installation and maintenance instructions 0020213395_04
VWF 57/4 230 V
VWF 87/4 230 V
VWF 117/4 230 V
Measuring current L1 & L2 for the com-
pressor and electronics plus maximum
1.3 A at X12 VR 40, maximum 0.9 A at X14
circulation pump and maximum 2.5 A at
TB X141, X143, X144 and X145 (L1 = L2)
(connection diagram 2)
16.6 A
23.8 A
29.6 A
Min. electrical power consumption of
compressor
1.40 kW
2.10 kW
2.60 kW
Max. electrical power consumption of
compressor
2.10 kW
3.10 kW
4.10 kW
Output levels for the auxiliary electric
heater (connection diagram 1; connection
diagram 2)
–
2.0 / 3.5 / 5.5 kW
–
2.0 / 3.5 / 5.5 / 7.0 /
9.0 kW
–
2.0 / 3.5 / 5.5 kW
–
2.0 / 3.5 / 5.5 / 7.0 /
9.0 kW
–
2.0 / 3.5 / 5.5 kW
–
2.0 / 3.5 / 5.5 / 7.0 /
9.0 kW
IP rating EN 60529
IP 10B
IP 10B
IP 10B
Hydraulics
VWF 57/4 230 V
VWF 87/4 230 V
VWF 117/4 230 V
Heating flow/return connection
G 1 1/2
″
G 1 1/2
″
G 1 1/2
″
Heat source flow/return connection
G 1 1/2
″
G 1 1/2
″
G 1 1/2
″
Heating expansion vessel connection
G 3/4
″
G 3/4
″
G 3/4
″
Heat source circuit/brine circuit
VWF 57/4 230 V
VWF 87/4 230 V
VWF 117/4 230 V
Brine content of the brine circuit in the
heat pump
2.5 l
3.1 l
3.6 l
Brine circuit materials
Cu, CuZn-Alloy, Stainless
Steel, EPDM, Brass, Fe
Cu, CuZn-Alloy, Stainless
Steel, EPDM, Brass, Fe
Cu, CuZn-Alloy, Stainless
Steel, EPDM, Brass, Fe
Min. brine fluid operating pressure
≥
0.07 MPa
(
≥
0.70 bar)
≥
0.07 MPa
(
≥
0.70 bar)
≥
0.07 MPa
(
≥
0.70 bar)
Max. brine fluid operating pressure
≤
0.3 MPa
(
≤
3.0 bar)
≤
0.3 MPa
(
≤
3.0 bar)
≤
0.3 MPa
(
≤
3.0 bar)
Max. electrical power consumption, brine
circuit pump
76 W
76 W
130 W
Brine pump type
High-efficiency pump
High-efficiency pump
High-efficiency pump
Building circuit/heating circuit
VWF 57/4 230 V
VWF 87/4 230 V
VWF 117/4 230 V
Heating circuit water contents in the heat
pump
3.2 l
3.9 l
4.4 l
Heating circuit materials
Cu, CuZn-Alloy, Stainless
Steel, EPDM, Brass, Fe
Cu, CuZn-Alloy, Stainless
Steel, EPDM, Brass, Fe
Cu, CuZn-Alloy, Stainless
Steel, EPDM, Brass, Fe
Permissible heating water condition
Do not add frost or
corrosion protection agents
to heating water. Soften the
heating water at water
hardnesses from
3.0
mmol/l (16.8° dH)
in
accordance with Directive
VDI 2035 Sheet 1.
Do not add frost or
corrosion protection agents
to heating water. Soften the
heating water at water
hardnesses from
3.0
mmol/l (16.8° dH)
in
accordance with Directive
VDI 2035 Sheet 1.
Do not add frost or
corrosion protection agents
to heating water. Soften the
heating water at water
hardnesses from
3.0
mmol/l (16.8° dH)
in
accordance with Directive
VDI 2035 Sheet 1.
Min. heating circuit operating pressure
≥
0.07 MPa
(
≥
0.70 bar)
≥
0.07 MPa
(
≥
0.70 bar)
≥
0.07 MPa
(
≥
0.70 bar)
Max. heating circuit operating pressure
≤
0.3 MPa
(
≤
3.0 bar)
≤
0.3 MPa
(
≤
3.0 bar)
≤
0.3 MPa
(
≤
3.0 bar)
Min. heating mode flow temperature
25
℃
25
℃
25
℃
Max. heating mode target flow temperat-
ure with compressor
65
℃
65
℃
65
℃
Max. heating mode target flow temperat-
ure with auxiliary electric heater
75
℃
75
℃
75
℃
Min. cooling mode flow temperature
5
℃
5
℃
5
℃