0020213395_04 Installation and maintenance instructions
65
Application limits for the heat pump: Heating (heat source = brine)
–
At the same volume flow rates in the heating circuit (
Δ
T 5 K or
Δ
T 8 K) and the brine circuit (
Δ
T 3 K). Operation of the
pump outside the application limits results in the heat pump being switched off by the internal control and safety devices.
–
Application limits for the heat pump: Heating (Brine heat source):
–
B15/W65
–
B25/W59
–
B25/W25
–
B
−
10/W25
–
B
−
10/W60
–
B
−
5/W65
O.3
Ground water heat source
Heat source circuit/brine circuit and ground water circuit
VWF 57/4 230 V
VWF 87/4 230 V
VWF 117/4 230 V
Heat source module
VWW 11/4 SI
VWW 11/4 SI
VWW 11/4 SI
Min. source inlet temperature (hot water)
in heating mode
10
℃
10
℃
10
℃
Max. source inlet temperature (hot water)
in heating mode
25
℃
25
℃
25
℃
Nominal flow of groundwater at
Δ
T 3 K
with W10W35
1,300 l/h
2,160 l/h
3,100 l/h
Brine fluid type
Ethylene glycol 30% vol.
Ethylene glycol 30% vol.
Ethylene glycol 30% vol.
Building circuit/heating circuit
VWF 57/4 230 V
VWF 87/4 230 V
VWF 117/4 230 V
Heat source module
VWW 11/4 SI
VWW 11/4 SI
VWW 11/4 SI
Nominal flow at
Δ
T 5 K
1,025 l/h
1,730 l/h
2,270 l/h
Max. remaining feed head with
Δ
T 5 K
0.08 MPa
(0.80 bar)
0.2193 MPa
(2.1930 bar)
0.4224 MPa
(4.2240 bar)
Nominal flow with
Δ
T 8 K
710 l/h
1,120 l/h
1,510 l/h
Max. remaining feed head with
Δ
T 8 K
0.062 MPa
(0.620 bar)
0.2103 MPa
(2.1030 bar)
0.4045 MPa
(4.0450 bar)
Min. volume flow during continuous oper-
ation at the application limits
710 l/h
1,120 l/h
1,510 l/h
Max. volume flow during continuous op-
eration at the application limits
1,025 l/h
1,730 l/h
2,270 l/h
Heating pump electrical power consump-
tion for W10/W35
Δ
T 5 K with an external
pressure loss of 250 mbar in the heating
circuit
24 W
37 W
49 W
Performance data
The following performance data is applicable to new products with clean heat exchangers.
Check conditions for determining the performance data in accordance with EN 14511
Installation: Connection pipes on the heat source side between VWF xx/4 and VWW xx/4 SI = 2 x 2 m (pipe internal diameter
= 32 mm), environment circuit pump setting: Heating mode: Factory setting (auto), Cooling mode: Factory setting (auto)
VWF 57/4 230 V
VWF 87/4 230 V
VWF 117/4 230 V
Heat source module
VWW 11/4 SI
VWW 11/4 SI
VWW 11/4 SI
Heat output W10/W35
Δ
T 5 K
5.72 kW
9.81 kW
13.04 kW
Effective power consumption for
W10/W35
Δ
T 5 K
1.26 kW
2.03 kW
2.73 kW
Coefficient of performance W10/W35
Δ
T
5 K/EN 14511
4.54
4.83
4.78
Heat output W10/W45
Δ
T 5 K
6.43 kW
9.81 kW
13.36 kW
Effective power consumption for
W10/W45
Δ
T 5 K
1.62 kW
2.57 kW
3.41 kW
Coefficient of performance W10/W45
Δ
T
5 K/EN 14511
3.97
3.82
3.92
Heat output W10/W55
Δ
T 8 K
6.48 kW
10.24 kW
13.77 kW
Содержание flexoTHERM exclusive VWF 57/4 230V