Inspection and maintenance
48
Installation and maintenance instructions ecoTEC pro 0020129672_03
12
Settings
Unit
Natural gas
(H)
Propane
CO
2
after 5 minutes full
load mode with
boiler front casing fitted
Vol.–%
9.2 +/
-
1.0
10.2 +/
-
0.5
CO
2
after 5 minutes full
load mode with boiler
front casing removed
Vol.–%
9.0 +/
-
1.0
10.0 +/
-
0.5
Set for Wobbe index Ws
kWh/m
3
15
22.5
CO value with full load
ppm
< 250
< 250
CO/CO
2
< 0.0031
< 0.0026
12.1 Factory gas setting
a
Danger!
Risk to life due to poisoning!
CO is an extremely toxic gas. Risk to life
due to excessive CO concentrations.
>
If you are not able to adjust the boiler
correctly and the flue gas values remain
higher than allowed in
¬ table 12.1
, call
the Vaillant Service Solutions
(0870 6060 777).
>
Do not start up the boiler!