Adapting the boiler to the heating installation
Installation and maintenance instructions ecoTEC pro 0020129672_03
43
11
T
Feed
(target)
[°C]
Set maximum burner anti-cycling time [min]
1
5
10
15
20
25
30
35
40
45
50
55
60
20
2.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
25
2.0
4.5
9.2
14.0
18.5
23.0
27.5
32.0
36.5
41.0
45.0
50.0
54.5
30
2.0
4.0
8.5
12.5
16.5
20.5
25.0
29.0
33.0
37.0
41.0
45.0
49.5
35
2.0
4.0
7.5
11.0
15.0
18.5
22.0
25.5
29.5
33.0
36.5
40.5
44.0
40
2.0
3.5
6.5
10.0
13.0
16.5
19.5
22.5
26.0
29.0
32.0
35.5
38.5
45
2.0
3.0
6.0
8.5
11.5
14.0
17.0
19.5
22.5
25.0
27.5
30.5
33.0
50
2.0
3.0
5.0
7.5
9.5
12.0
14.0
16.5
18.5
21.0
23.5
25.5
28.0
55
2.0
2.5
4.5
6.0
8.0
10.0
11.5
13.5
15.0
17.0
19.0
20.5
22.5
60
2.0
2.0
3.5
5.0
6.0
7.5
9.0
10.5
11.5
13.0
14.5
15.5
17.0
65
2.0
1.5
2.5
3.5
4.5
5.5
6.5
7.0
8.0
9.0
10.0
11.0
11.5
70
2.0
1.5
2.0
2.5
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
75
2.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
11.2 Effective burner anti-cycling times
11.1.6 Setting the maintenance interval
You can define maintenance intervals for the ecoTEC pro.
After the set burner operating hours have elapsed, in addi-
tion to the current flow temperature, the maintenance sym-
bol (open-end spanner) appears in the display and this
shows that the boiler must be serviced. The display on the
eBUS controller (accessory) shows the information "Mainte-
nance" "MAIN".
Heat demand
Number of
persons
Burner operating hours until the
next inspection/service
(depending on the system type)
5.0 kW
1 - 2
2 - 3
1,050 h
1,150 h
10.0 kW
1 - 2
2 - 3
1,500 h
1,600 h
15.0 kW
2 - 3
3 - 4
1,800 h
1,900 h
20.0 kW
3 - 4
4 - 5
2,600 h
2,700 h
25.0 kW
3 - 4
4 - 6
2,800 h
2,900 h
> 27.0 kW
3 - 4
4 - 6
3,000 h
3,000 h
11.3 Guideline values for operating hours
>
Set the operating hours until the next service using diag-
nosis code "d.084".
Guideline values for the setting can be found in
¬ table 11.3
. The values stated correspond to an average
boiler operating time of one year.
You can set the operating hours in increments of ten from
0 to 3,000 h.
If you do not enter a figure under diagnosis code "D.084"
but instead enter the symbol "–", then the "Maintenance
display" function is not active.
i
On completion of the set operating hours, you
must set the maintenance interval again in diag-
nosis mode.
11.1.7 Setting the by-pass valve
The boilers have a by-pass valve.
The pressure is adjustable in the range between 17.0 MPa
(170 mbar) and 35.0 MPa (350 mbar). Approx. 25.0 MPa
(250 mbar) is pre-set (mid-position). The pressure changes
by approx. 1.0 MPa (10 mbar) each time the adjusting screw
is rotated. By turning right, the pressure increases and turn-
ing left decreases it.
1
11.1 Setting the by-pass valve