Appendix
34
Installation
and
maintenance
instructions
ecoTEC
pro
0020244995_02
Code Parameter
Values or explanations
Default
setting
Own setting
D.076 Device Specific Number
Device specific number = DSN
7 = 24 (VUW GB 246/5-3 A); VUW 246/5-3 (H-GB)
ecoTEC pro 24
22 = 28 (VUW GB 286/5-3A); VUW 286/5-3 (H-GB)
ecoTEC pro 28; VUW 286/5-3 (P-GB) ecoTEC pro 28
26 = 30 (VUW GB 306/5-3)
Not ad-
justable
D.077 DHW partial load
Adjustable cylinder charging output in kW
D.078 DHW max. flow temperature
Limit on cylinder charging temperature in °C
50 °C
–
80 °C
Note
The chosen value must be at least 15 K or 15 °C above
the set cylinder target value.
75 °C
D.080 Heating operating hours
In hours (h)
Not ad-
justable
D.081 DHW operating hours
In hours (h)
Not ad-
justable
D.082 Heating burner starts
Number of burner start-ups
Not ad-
justable
D.083 DHW burner starts
Number of burner start-ups
Not ad-
justable
D.084 Maintenance in
Adjustment range: 0 to 3000 hrs and "---" for deactivated
„---”
D.088 Min. DHW flow rate
Start delay for hot water draw-off detection via impeller
(only products with integrated hot water generation)
0 = 1.5 l/min and no delay,
1 = 3.7 l/min and 2 sec. delay
1.5 l/min and
no delay
D.090 eBUS controller
Status of digital controller
Recognised, not recognised
Not ad-
justable
D.091 Status DCF77
Status of DCF with external temperature sensor connec-
ted
No reception
Reception
Synchronised
Valid
Not ad-
justable
D.092 actoSTOR communication status
actoSTOR
module detection
0 = Not connected
1 = Connection error: No communication via PeBus,
actoSTOR
module was previously detected
2 = Connection active
Not ad-
justable
D.093 Adjust Device Specific Number
Device Specific Number (DSN)
Setting range: 0 to 99
D.094 Clear fault history
Delete fault list
0 = No
1 = Yes
D.095 Software version: PeBUS parti-
cipant
PCB (BMU)
Display (AI)
actoSTOR
(APC)
HBI/VR34
Not ad-
justable
D.096 Reset to factory settings?
Reset all adjustable parameters to factory setting
0 = No
1 = Yes