9 Inspection and maintenance
26
Installation and maintenance instructions ecoTEC plus 0020134823_04
8.6
Burner anti-cycling time
8.6.1
Setting the burner anti-cycling time
To prevent frequent switching on and off of the burner and
thus prevent energy losses, an electronic restart lockout
is activated for a specific period each time the burner is
switched off. You can adjust the burner anti-cycling time to
the conditions of the heating installation. The burner anti-
cycling time is only active for the heating mode. You can set
the maximum burner anti-cycling time under
D.002
(default
setting: 20 min.). The effective burner anti-cycling times with
respect to the target flow temperature and the maximum set
burner anti-cycling time can be found in the following table:
T
Flow
(target)
[°C]
Set maximum burner anti-cycling time [min]
1
5
10
15
20
25
30
30
2.0
4.0
8.5
12.5
16.5
20.5
25.0
35
2.0
4.0
7.5
11.0
15.0
18.5
22.0
40
2.0
3.5
6.5
10.0
13.0
16.5
19.5
45
2.0
3.0
6.0
8.5
11.5
14.0
17.0
50
2.0
3.0
5.0
7.5
9.5
12.0
14.0
55
2.0
2.5
4.5
6.0
8.0
10.0
11.5
60
2.0
2.0
3.5
5.0
6.0
7.5
9.0
65
2.0
1.5
2.5
3.5
4.5
5.5
6.5
70
2.0
1.5
2.0
2.5
2.5
3.0
3.5
75
2.0
1.0
1.0
1.0
1.0
1.0
1.0
T
Flow
(target)
[°C]
Set maximum burner anti-cycling time [min]
35
40
45
50
55
60
30
29.0
33.0
37.0
41.0
45.0
49.5
35
25.5
29.5
33.0
36.5
40.5
44.0
40
22.5
26.0
29.0
32.0
35.5
38.5
45
19.5
22.5
25.0
27.5
30.5
33.0
50
16.5
18.5
21.0
23.5
25.5
28.0
55
13.5
15.0
17.0
19.0
20.5
22.5
60
10.5
11.5
13.0
14.5
15.5
17.0
65
7.0
8.0
9.0
10.0
11.0
11.5
70
4.0
4.5
5.0
5.5
6.0
6.5
75
1.0
1.0
1.0
1.0
1.0
1.0
Note
The remaining burner anti-cycling time following a
regular shutdown in heating mode can be called
up under
D.067
.
8.6.2
Resetting the remaining burner anti-cycling
time
1st option
Menu
→
Reset anti-cycl. time
The current burner anti-cycling time appears in the display.
▶
Confirm the burner anti-cycling time reset by pressing
(
Select
).
2nd option
▶
Press the fault clearance key.
8.7
Setting the maintenance interval
If you set the maintenance interval, the message that the
product must be serviced appears in the display, together
with the maintenance symbol
, after a configurable number
of burner operating hours. The display on the eBUS control-
ler shows the information
Maintenance MAIN
.
▶
Set the operating hours until the next maintenance work
is due using
D.084
. You can set the operating hours in
increments of ten from 0 to 3010 h (hours).
If you do not set a numerical value, but instead set the sym-
bol "
–
", the "
Maintenance display
" function is not active.
Note
On completion of the set operating hours, you
must set the maintenance interval again.
8.8
Setting the pump output
The product can be equipped with a pump group with a mod-
ulating or high-efficiency pump (accessories). Both pumps
are fully modulating and are actuated depending on the heat
requirement.
The remaining feed head of this pump group is designed so
that the full heat output is transported as far as the system
separation.
You can find the remaining feed head of the pumps in the
section "Hydraulic connection" (
→
Page 13).
8.9
Handing the product over to the operator
1.
When you have finished the installation, attach the
sticker supplied (835593) to the front of the product in
the operator's language.
2.
Explain to the operator how the safety devices work and
where they are located.
3.
Inform the operator how to handle the product. Answer
any questions the operator may have. In particular,
draw attention to the safety information which the op-
erator must follow.
4.
Inform the operator of the necessity to have the product
maintained according to the specified intervals.
5.
Pass all of the instructions and documentation for the
product to the operator for safe-keeping.
6.
Inform the operator about measures taken to ensure the
supply of combustion air and flue gas guiding, and in-
struct the operator that he must not make any changes.
9
Inspection and maintenance
Auxiliary service equipment:
You require the following tool for the inspection and mainten-
ance:
–
SW8 socket with extension
–
Torx screwdriver 20, 25 and 30
–
5 mm hexagon socket
▶
Carry out all inspection and maintenance work in the
order shown in the table "Overview of inspection and
maintenance work".