3.8 Flue termination
The following details refer to both flue systems.
a. The terminal must be positioned such that the produc-
ts of combustion can disperse freely at all times.
b. A plume of water vapour will sometimes be visible
from the flue terminal. Positions where this could be a
nuisance should be avoided.
c. If the terminal is fitted less than 2 m above a balcony,
above ground or above a flat roof to which people
have access then a suitable terminal guard must be
provided and fitted (made by Tower Flue Components,
Tonbridge, TN9 1TB).
Fig. 3.7 Flue termination
Note:
Vertical flues must not terminate within 600
mm of an openable window, air vent or any other
ventilation opening.
The flue assembly shall be so placed or sheilded as to
prevent ignition or damage to any pary of the building.
Terminal position
mm
A
Directly below an opening, above an opening or
horizontal to an opening, air brick, opening window, etc. 300
B
Below gutters, soil pipes or drain pipes
75
C
Below eaves
200
D
Below balconies
200
E
From vertical drain pipes and soil pipes
25
F
From internal or external corners
300
G
Above ground, roof or balcony
300
H
From a surface facing a terminal
600
I
From a terminal facing a terminal
1200
K
Vertically from a terminal on the same wall
1500
L
Horizontally from a terminal on the same wall
300
M
Distance from adjacent for vertical Flue
500
Table 3.3 Terminal position for a fan assisted concentric flue
A
BCD
A
G
H, I
F
J
B
F
M
L
L
K
K
G
G
F
F
E
A
A
15
3
0
880
70
70
1103
70
15
13
General requirements 3
Instructions for installation and servicing ecoMAX
13
83 41 77_12 GB04.04.qxd 22.09.2004 12:34 Uhr Seite 13