6 Boiler Location and Ventilation

Instructions for Use, Installation and Servicing ecoMAX pro

12

Fig. 6.1

*

*

*

*

Increase to 25mm clearance from
comb ustible material.

MINIMUM CLEARANCE  FROM
PERMANENT SURFACES

† A removable compartment door can be
placed at least 5mm in front of the appliance.

5

5

600

200**

20

20

200

** 220mm above the boiler when utilising the 
     125mm flue system

5

6 Boiler Location and Ventilation

6.1 Boiler Location

The boiler may be installed in any room although 
particular attention is drawn to the requirements of the
current issue of BS7671, IEE Wiring Regulations,  the
electrical provisions of the Building Regulations
(Scotland), and in IE the current edition of IS 813 and
the ETCI rules, with respect to the installation of a boiler
in a room containing a bath or a shower. Any electrical
switch or boiler control using mains electricity should be
so situated that a person using the bath or shower can-
not touch it.
The boiler must be mounted on a flat wall, which is 
sufficiently robust to take its total weight. The boiler
may be installed on a combustible wall, subject to the
requirements of the Local Authorities and Building
Regulations.
The boiler is not suitable for fitting outdoors.

6.2 Clearances

The boiler should be positioned so that at least the 
minimum operational and servicing clearances are 
provided, see Fig. 6.1.
Additional clearances may be beneficial around the 
boiler for installation and servicing.
For flue installations where external access is not 
practicable, consideration should be given for the space
required to insert the flue internally, which may 
necessitate clearance larger than those specified in 
Fig. 6.1.

6.3 Timber Frame Buildings

If the boiler is to be installed in a timber frame building
it should be fitted in accordance with the Institute of Gas
Engineers document IGE/UP/7/1998.

6.4 Room Ventilation

The boiler is room sealed, so when it is installed in a
room or space, a permanent air vent is not required. 

6.5 Compartment Ventilation

If the boiler is installed in a compartment, a permanent
air vent is not required.
Leave existing air vents.

Содержание ecoMAX pro SERIES

Страница 1: ...To be left with the user Instructions for Use Installation and Servicing ecoMAX pro Wall hung condensing boilers for traditional open vented systems GB 18 E 28 E...

Страница 2: ...alve 11 5 9 2 Expansion Vessel 11 5 9 3 Pressure Gauge 11 5 9 4 Domestic Hot Water Cylinder 11 5 9 5 Water Makeup 11 5 9 6 Filling a Sealed Water System 11 5 10 Water Treatment 11 Page 6 Boiler Locati...

Страница 3: ...ral 24 15 2 Spark Electrode 24 15 3 Burner 25 15 4 Combustion Chamber and Heat Exchanger 26 15 5 Inner Casing Panel Seal Check 26 16 Combustion analysis 27 17 Fault Finding 28 17 1 Status Mode 28 17 2...

Страница 4: ...ion 1 1 Boiler 2 1 Hanging bracket 3 1 Flue connection adaptor 4 1 Instruction booklet 5 2 Guarantee card and envelope and log book 6 1 Template 7 1 Screws wallplugs 8 1 Gas service valve and compress...

Страница 5: ...d by Notified body 0086 Product production certified by Notified body 0086 The CE mark on this appliance shows compliance with 1 Directive 90 396 EEC on the approximation of the laws of the Member Sta...

Страница 6: ...is boiler contains metal parts components and care should be taken when handling and cleaning with particular regard to edges Sealed Components Under no circumstances must the User interfere with any...

Страница 7: ...y be used to switch off the boiler however it is preferable to leave the electrical supply on whenever possible to permit operation of the built in frost protection and daily pump exercise programme F...

Страница 8: ...ons Northern Ireland Water Supply Water Fittings Regulations Water Bylaws The Health and Safety at Work Act Control of Substances Hazardous to Health The Electricity at Work Regulations the current IE...

Страница 9: ...household draining system If this is not practical discharge can be made externally into the hou sehold drainage system or a purpose designed soak away see Section 10 3 for more details 4 7 Heating Sy...

Страница 10: ...n the current edition of IS 813 and the current Building Regulations must be followed If fitting to an existing system the local authority should be informed Note ecoMAX pro boilers are not suitable f...

Страница 11: ...5449 BS6759 BS6798 and BS7074 Part 1 and 2 For IE your attention is drawn to the current edition of IS 813 See Fig 5 4 for a suggested layout Fig 5 4 5 9 1 Safety Valve A safety valve must be fitted t...

Страница 12: ...mounted on a flat wall which is sufficiently robust to take its total weight The boiler may be installed on a combustible wall subject to the requirements of the Local Authorities and Building Regula...

Страница 13: ...ny part of the building Fig 7 3 A BCD A G H I F J B F M L L K K G G F F E A A 7 Flue 7 1 Flue Position and Length The standard horizontal flue is fitted onto the top of the boiler See Fig 7 1 and 7 2...

Страница 14: ...690 mm 303 906 87 elbow 303 910 Two 45 bends 303 911 Standard horizontal air flue duct with elbow and terminal 800 mm 303 930 Additional accessories are available 8 Installation Preparation 8 1 Unpack...

Страница 15: ...FF WALL TEMPLATE HANGING BRACKET WALL TEMPLATE 127 900 176 3 1 Fig 8 2 8 3 Rear flue exit Mark the position of the air flue duct and its circumference 8 4 Other flue options Flue instructions for othe...

Страница 16: ...TOR CAP GAS SERVICE COCK LINER SPIGOT CONDENSATE DRAIN CONNECTION 10 3 Condensate Drain Connection The condensate drain connection is at the rear of the boiler see Fig 10 1 A 21 5 mm plastic overflow...

Страница 17: ...aximum permitted straight flue length is 10 metres For each 90 elbow or pair of 45 bends fit ted the maximum length must be reduced by 1 metre Note When using elbows bends any horizontal exten sion pi...

Страница 18: ...ll amount of sealant Fig 11 4 Elevated horizontal flue 11 3 Flue Assembly The flue assembly is a push fit design with securing collars Remove all burrs from cut pipes Fig 11 5 shows the components sup...

Страница 19: ...system components must be of an approved type and meet the requirements of the current IEE Wiring Regulations and in IE the current edition of the ETCI rules Electrical components have been tested to...

Страница 20: ...must be retightened and tested for soundness The boiler itself does not require purging as this will be done by the automatic burner sequence control 13 4 Initial Lighting The lighting procedure of t...

Страница 21: ...west part of the system Fill and vent the system as described previously Lock or remove the handles from controls valve A and bypass valve B to prevent unauthorised adjustment 13 7 User Controls and O...

Страница 22: ...clockwise 5 1 2 turns Ensure that the gas analyser is set to the correct fuel setting Propane To obtain conversion follow the procedure as below Connect a CO2 combustion analyser to the test point on...

Страница 23: ...carefully adjust the CO2 with the B offset adjustment using a 2 mm allen key to 10 5 rotate clockwise to increase After checking the combustion press and hold the mode button for 10 seconds to return...

Страница 24: ...water carrying components ensu re that the water is kept away from all electrical com ponents Always use new seals and O rings when replacing parts Always test for gas soundness and always carry out f...

Страница 25: ...five combustion chamber front securing nuts see Fig 15 5 Fig 15 2 Fig 15 3 CONTROL PANEL SERVICE POSITION SECURING SCREW 4 OFF CHASSIS FRONT CONDENSE TRAP GAS SERVICE COCK GAS SUPPLY PIPE IN GAS PIPE...

Страница 26: ...se trap taking care not to spill any water which may be left in the unit As the unit is lifted remove the flexible pipe on the outlet Remove the cap at the base of the condense trap Remove any solids...

Страница 27: ...r demand With the boiler interface in normal operating mode press and hold the mode button for 10 seconds until a flashing 0 appears Fig 16 1 Press the key and scroll through until 96 installer mode i...

Страница 28: ...icity supply to the boiler is on and a supply of 230V is present at the boiler terminal strip 3 Check that the gas supply to the boiler is on that it has been correctly purged and that an inlet pressu...

Страница 29: ...10 Adaptive heating or night day switch No function adjustable 11 Night day setpoint Delta value No function adjustable 12 Central heating flow temperature C Read only 13 Central heating return tempe...

Страница 30: ...fault memory screens are now available to be viewed memory 1 being the most recent Within each memory screen 5 additional screens provide further information to assist the installer engineer No Memor...

Страница 31: ...e Faulty interface Faulty main PCB processor Check fan F12 No reception by the local user interface As F 11 F13 Main board fault As F 11 F14 Central heating flow t 95 C System fault Possible external...

Страница 32: ...inding Instructions for Use Installation and Servicing ecoMAX pro 32 Fig 17 3 Fan control PCB DC fan supply room stat frost stat 230 V interface PCB Main PCB Main user display interface br b 17 4 Faul...

Страница 33: ...cription 1 190260 Fan assembly 2 090750 Spark electrode 3 091258 Igniter unit 4 053574 Gas control valve 5 101771 Heating flow return NTC 2 6 101191 Overheat stat 7 130837 Main PCB 8 287452 Fan contro...

Страница 34: ...y G20 Gross CV s t 37 8 37 8 MJ m3 Maximum gas rate 2 00 3 02 M3 h Minimum gas rate 0 53 0 56 M3 h Burner CO2 Case on 9 0 0 2 9 0 0 2 Gas connection 15 mm Compression 15 mm Compression Water connectio...

Страница 35: ...Instructions for Use Installation and Servicing ecoMAX pro 35...

Страница 36: ...3 49 39 GB 01 05 2004 Subject to alteration Head Office Vaillant Ltd Service Solutions 0870 6060 777 Vaillant House Trident Close Medway City Estate Rochester Kent ME2 4EZ Technical Advice 01634 29239...

Отзывы: