4 Set-up
8
Installation and maintenance instructions ecoFIT pure 0020230535_05
4.4
Dimensions
11
2
183,5
71
375
78
33,5
602
220
150
32,5
100
157,5
320
1
2
3
4
5
6
1
Condensate discharge
2
Gas connection
3
Heating return
4
Heating flow
5
Connection on the back
of the air/flue pipe
6
Connection on the top
of the air/flue pipe
4.5
Minimum clearances
C
C
A
B
D
Minimum clearance
A
150 mm (top air/flue connection)
75 mm (rear air/flue connection) *
B
150 mm
C
5 mm
(70 mm, if the side sections have to be removed)
D
600 mm
* Dimension A can be reduced to 20 mm if there is a removable
surface above the product.
4.5.1
Clearance from combustible components
It is not necessary to maintain a clearance between the
product and components made of combustible materials that
goes beyond the minimum clearances (
→
Page 8).
4.6
Using the mounting template
▶
Use the mounting template to ascertain the locations at
which you need to drill holes.
4.7
Wall-mounting the product
Note
If you are using the rear air/flue connection, in-
stall the air/flue pipe before you wall-mount the
product.
1.
Only use fixing material that is permitted for the wall.
2.
Check the load-bearing capacity of the wall.
3.
Note the total weight of the product.