Clearances for connecting the siphon
150L
Max. dimension
(A)
720 mm
Dimension (B)
770 mm
Max. dimension
(C)
300 mm
Condensed water forms during combustion. The condensed
water discharge pipe routes this condensed water to the
waste-water connection via a funnel.
▶
Use PVC or another material that is suitable for draining
the non-neutralised condensed water.
▶
Only use corrosion-resistant piping material for removing
condensate.
▶
If it cannot be guaranteed that the materials are suitable,
install a system for neutralising the condensed water.
▶
Connect the condensed water discharge pipe
(1)
to a
suitable drain siphon
(2)
.
▶
Ensure that the condensed water in the drain pipework is
drained properly.
5.5
Air/flue system
5.5.1
Installing the air/flue pipe
▶
Install the air/flue pipe as described in the separate set-
up instructions for the air/flue pipe.
5.5.2
Changing the connector for the air/flue pipe
Note
The products are fitted with a 60/100 mm dia-
meter connector as standard.
A
B
C
1.
Insert a screwdriver into the slot between the test
points.
2.
Carefully exert pressure on the screwdriver
(A)
.
3.
Turn the connector anti-clockwise
(B)
as far as it will go
and then remove it by pulling it upwards
(C)
.
4.
Insert the new connector. In doing so, pay attention to
the latching lugs.
5.
Turn the connector clockwise until it clicks into position.
5.5.3
Information and specifications for installing
the B23P
Applicability:
Germany
Pipe lengths in the B23P installation (
→
Page 43)
The flue gas system must at least correspond to the classi-
fication T 120 P1 W 1 in accordance with EN 1443.
The maximum pipe length (straight pipe only) corresponds to
the maximum permitted flue gas pipe length without any el-
bows. If elbows are used, the maximum pipe length must be
reduced in accordance with the dynamic flow characteristics
of the elbows. Elbows must not be connected directly after
one another as this method dramatically increases pressure
losses.
In particular, if the flue pipe is installed in cold rooms or out-
side of the building, the freezing point on the surface of the
inside of the pipe may be reached. A proven design in ac-
cordance with EN 13384-1 for a maximum boiler load at a
flue gas temperature of 40 °C must be used to prevent this
problem. The product must not be connected to a cascade
flue gas system that is being used by other units.
▶
Observe the applicable international, national and local
regulations for flue gas systems, in particular for installa-
tions in living rooms. Inform the operator how to correctly
operate the product.
5.6
Electrical installation
Only qualified electricians may carry out the electrical install-
ation.
Danger!
Risk of death from electric shock!
Touching live connections may cause serious
personal injury. Since mains connection ter-
minals L and N remain live even if the on/off
button is switched off:
▶
Switch off the power supply.
▶
Secure the power supply against being
switched on again.