10.1
Technical data for VIH S 300/400/500 and
VIH R 300/400/500
Units
VIH S
VIH R
VIH S 300
VIH S 400
VIH S 500
VIH R 300
VIH R 400
VIH R 500
Nominal cylinder capacity
l
300
400
500
300
400
500
Actual cylinder capacity
l
289
398
484
295
404
496
Maximum operating pressure – cylinder bar
10
10
10
10
10
10
Maximum operating pressure - heating
bar
10
10
10
10
10
10
Max. hot water temperature
°C
85
85
85
85
85
85
Maximum hot water flow temperature
°C
110
110
110
110
110
110
Standby energy loss
kWh/d
1.9
2.1
2.3
1.8
2.0
2.2
Heating heat exchanger:
Heating area of the heat exchanger
m
2
0.7
0.7
1.0
1.6
1.5
2.1
Heating water capacity of the heat ex-
changer
l
4.7
4.5
6.6
10.7
9.9
14.2
Pressure loss in the heat exchanger at
max. hot water demand
mbar
11
11
16
75
75
125
Heating medium flow
l/h
900
900
1250
2000
2000
2700
Initial hot water output at 45/10 °C
1)
l/10min
195
190
215
462
519
591
Continuous hot water output at a heat-
ing water temperature of 85/65 °C
2)
kW
20
21
29
46
46
62
Continuous hot water output at a heat-
ing water temperature of 85/65 °C
2)
l/h
491
516
712
1130
130
1523
Output characteristic figure
1)
N
L
2.0
3.5
4.7
11.0
15.0
19.0
Solar heat exchanger:
Heating area of the heat exchanger
m
2
1.6
1.5
2.1
Heating water capacity of the heat ex-
changer
l
10.7
9.9
14.2
Pressure loss in the heat exchanger in
solar mode with solar fluid
mbar
< 10
< 10
< 10
Solar fluid flow
l/h
200
300
500
Connections
Cold water and hot water connection
Thread
R1
R1
R1
R1
R1
R1
Secondary return connection
Thread
R
3
/
4
R
3
/
4
R
3
/
4
R
3
/
4
R
3
/
4
R
3
/
4
Flow and return connections
Thread
R1
R1
R1
R1
R1
R1
Cylinder dimensions:
Width with casing
mm
660
810
810
660
810
810
Depth with casing
mm
725
875
875
725
875
875
Height
mm
1775
1470
1775
1775
1470
1775
Outer diameter of tank without insula-
tion
mm
500
650
650
500
650
650
Weight (incl. packaging and insulation)
kg
150
169
198
125
145
165
Weight when filled and ready for opera-
tion
kg
439
567
682
420
549
661
Table 10.1 Technical data for VIH S 300/400/500 and
VIH R 300/400/500
1)
per DIN 4708, Part 3
2)
Temperature difference between hot and cold water: 35 K