background image

 

 
 

 

INSTALLATION, OPERATION and 

MAINTENANCE  

Figure 922 Air Release Valves 

 
 

INTRODUCTION 

This  manual  will  provide  the  information  to 
properly  install,  operate  and  maintain  the  valve 
to  ensure  a  long  service  life.      The  Air  Release 
Valve is ruggedly constructed to provide years of 
trouble-free 

operation 

with 

minimal 

maintenance.  
 
These  Air  Release  Valves  are  not  intended  for 
use with fluids containing suspended solids such 
as  wastewater and  sewage.   The  GA  Industries 
Figure  925,  927  or  929  Air  Release  Valves  are 
recommended for such applications.   

 

CAUTION 

The  valve  is  NOT  recommended  for  use  with 
toxic  fluids,  fuels  or  fluids  containing  hazardous 
gases 
 

CAUTION 

The  valve  will not  function  if  used  at  a  pressure 
higher  than  the  maximum  working  pressure 
indicated on the nameplate. 
 
The  Shop  Order  (SO)  Number,  Figure  Number, 
size  and  pressure  rating  are  stamped  on  a 
nameplate attached to the valve.  Please refer to 
the SO number when ordering parts.  
 

DESCRIPTION OF OPERATION

 

The  Air  Release  Valve  is  designed  to 
automatically  vent  air  that  has  accumulated 
within  the  valve.    These  valves  are  usually 
installed  at  high  points  in  the  system  where  air 
tends  to  collect.    The  valve  as  shipped  is 
”normally  open”  and  will  vent  air  through  its 
orifice  at  the  top  of  the  valve.    The  float  rises 
when  water  enters  the  valve  and  closes  the 
orifice.    Air  from  the  system  accumulates  in the 
valve forcing the water level down until the float 
drops  and  opens  the  venting  orifice.    As  air  is 
released the water level rises lifting the float and 
re-closing the valve.  
 
This  sequence  occurs  as  often  as  necessary  to 
release air that has collected in the valve. 
 

 
 
RECEIVING AND STORAGE 

Inspect  the  valve  upon  receipt  for  damage 
during  shipment.    Carefully  unload  all  valves  to 
the ground without dropping.   
 
The  valves  should  remain  in  a  clean,  dry  and 
weather  protected  area  until  installed.    For  long 
term storage (greater than 6 months) the rubber 
surfaces  of  the  seat  should  be  coated  with  a 
non-toxic  lubricant  such  as  "SuperLube"  made 
by  Synco  Chemical.    Do  not  expose  the  rubber 
parts to sunlight or ozone. 
 

INSTALLATION 

The  Figure  922  is  standard  with  NPT  screwed 
connections.    An  optional  flange  pipeline 
connection is available on special order.  
 
Consult  the  drawings  of  record  to  verify  the 
configuration supplied and installed. 
 
The valve must be installed in an upright vertical 
orientation,  normally  at  a  high  point  in  the 
system.   
 
If  installed  outdoors,  below  ground  in  a  vault  or 
in an unheated area, adequate freeze protection 
must  be  provided.    Some  discharge  of  water 
may  occur  during  operation  so  the  valve  outlet 
should be piped to an adequate drain. 
 
An  isolating  valve  should  be  installed  between 
the valve and the pipeline or system to facilitate 
maintenance.    
 
Carefully  screw  threaded  end  valves  onto  pipe 
nipple using compatible thread sealant.  Tighten 
valve  using  wrench  flats.    DO  NOT  OVER-
TIGHTEN. 
 
Flat-faced  flanged  valves  should  be  mated  with 
flat-faced  flanges  and  full-face  gaskets.    If  ring 
gaskets  are  used  the  bolt  material  shall  be 
ASTM  A307  Grade  B  (or  equivalent).    Higher 
strength  bolting  should  only  be  used  with  full-
face gaskets.   
 