STO AND SS1 SAFETY FUNCTIONS
vacon • 29
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Figure 13. STO connection example 2
Figure 14. STO connection example 3
Cable recommendation:
See Table 6 for connections where shielded cable is required. In cases where the shield is marked
as being required, use the shield to separate the STO input channels from each other as shown in
Figure 15.
Type
For example one of the following:
• 2x2x0.75mm
2
(18 AWG) low voltage cable with two
individually shielded twisted pairs
• 2x2x0.75mm
2
(18 AWG) low voltage, unshielded,
twisted pair cable
• two separate 2x0.75mm
2
(18 AWG) shielded or
unshielded twisted pair cables.
SAFETY ACTUATOR
OPTAF
CHANNEL 1
SW P
+24V
+24V
OV
OV
SW M
SD1+
SD1-
OPTAF
CHANNEL 2
SD2+
SD2-
11968_uk
SAFETY ACTUATOR
OPTAF
CHANNEL 1
SW P
+24V
+24V
SW P
SD1+
SD1-
OPTAF
CHANNEL 2
SD2+
SD2-
OV
11969_uk
Содержание OPTAF
Страница 1: ...vacon nx ac drives optaf sto and atex option board user manual ...
Страница 2: ......
Страница 8: ...vacon 6 GENERAL Local contacts https www danfoss com en contact us contacts list ...
Страница 9: ...GENERAL vacon 7 Local contacts https www danfoss com en contact us contacts list ...
Страница 10: ...vacon 8 GENERAL Local contacts https www danfoss com en contact us contacts list ...
Страница 11: ...GENERAL vacon 9 Local contacts https www danfoss com en contact us contacts list ...
Страница 12: ...vacon 10 GENERAL Local contacts https www danfoss com en contact us contacts list ...