10 • vacon
Parameter lists
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
3.3
Input signals (Control keypad: Menu M2 G2.2)
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.2.1
0
1
1
1590 0=Normally open
1=Normally closed
P2.2.2
0
10
3
301
0=Motor pot. UP
(cc
)
1=Reverse
2=External fault CC
3=External fault OC
4=Fault reset
5=Run enable
6=Preset speed 1
7=DC brake cmnd
8=PID disable
9=PID disable, go to preset
speed
10=PID keypad ref 2
P2.2.3
0
1
0
1572 0=Preset Speed 1
1=Fault Reset
P2.2.4
0
3
1
379
0=Signal range 0-20mA
1=Signal range 4-20mA
2=0-10V
3=2-10V
P2.2.5
0
1
0
1544
P2.2.6
0,00 P2.2.6 % 0,00
380
P2.2.7
0,00 100,00 % 100,00
381
P2.2.8
0
1
0
387
0=Not inverted
1=Inverted
P2.2.9
0,00
10,00
s
1,00
378
0=No filtering
P2.2.10
0
1
1
390
0=Signal range 0-20mA
1=Signal range 4-20mA
P2.2.11
0
1
1
1545
P2.2.12
0,00 P2.2.6 % 0,00
391
P2.2.13
0,00 100,00 % 100,00
392
P2.2.14
0
1
0
398
0=Not inverted
1=Inverted
P2.2.15
0,00
10,00
s
1,00
389
0=No filtering
P2.2.16
0
59
1558 TTF programming method
P2.2.17
0
1
1
1520 0=Signal range 0-20mA
1=Signal range 4-20mA
P2.2.18
0
1
0
1546
P2.2.19
0,00 P2.2.18 % 0,00
1517
P2.2.20
P2.2.17 100,00 % 100,00
1518
P2.2.21
0
1
0
1529 0=Not inverted
1=Inverted
P2.2.22
0,00
10,00
s
1,00
1526 0=No filtering
P2.2.23
0
1
0
121
Keypad freq ref selection:
0=Reference from Keypad
1=FB reference
P2.2.24
0
1
1
122
Fieldbus frequency
reference selection:
0=Reference from Keypad
1=FB reference
Table 11. Input signals, G2.2
*Remember to place jumpers of block X2 accordingly.
See the product's user's manual.