Table 27: The cable and fuse sizes for Vacon
®
NXS and NXP, North America
Frame
Type
Fuse
Class(T/J)
Mains, Motor and
brake resistor
cable Cu [AWG]
Terminal cable size
Mains cable
terminal [AWG]
Grounding
terminal [AWG]
FR6
0004 6—0007 6
AJT10
3*14 AWG + 14 AWG 14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0010 6—0013 6
AJT15
3*14 AWG + 14 AWG 14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0018 6
AJT20
3*12 AWG + 12 AWG 14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0022 6
AJT25
3*10 AWG + 10 AWG 14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0027 6—0034 6
AJT35
3*8 AWG + 8 AWG
14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
FR7
0041 6
AJT50
3*8 AWG + 8 AWG
14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
10 AWG - 1 AWG
0052 6
AJT70
3*6 AWG + 6 AWG
14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
10 AWG - 1 AWG
FR8
0062 6—0080 6
AJT90
3*4 AWG + 6 AWG
4 AWG - 3/0 AWG
Cu/Al
10 AWG - 3/0
AWG
0100 6
AJT110
3*2 AWG + 6 AWG
4 AWG - 3/0 AWG
Cu/Al
10 AWG - 3/0
AWG
FR9
0125 6—0144 6
0170 6
AJT200
3*3/0 AWG + 1/0
AWG
3/0 AWG - 350kcmil
Cu/Al
10 AWG - 3/0
AWG
0208 6
AJT250
3*30 2/0
AWG
3/0 AWG - 350kcmil
Cu/Al
10 AWG - 3/0
AWG
VACON · 52
POWER CABLING
5
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205