Control keypad
vacon • 77
24-hour support: +358-40-8371 150 • Email: [email protected]
7
Status Word
15 14 13 12 11 10 9 8 7
6
5
4
3
2
1
0
- - - - - - - - F
Z
AREF
W
FLT
DIR
RUN
RDY
Information about the status of the device and messages is indicated in the
Status word
. The
Status
word
is composed of 16 bits the meanings of which are described in the table below:
Actual speed
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
MSB
LSB
This is actual speed of the frequency converter. The scaling is –10000...10000. In the application, the
value is scaled in percentage of the frequency area between set minimum and maximum frequency.
Control word
15 14 13 12 11 10 9 8 7 6 5 4 3 2
1
0
- - - - - - - - - - - - -
RST
DIR
RUN
In Vacon applications, the three first bits of the control word are used to control the frequency
converter. However, you can customise the content of the control word for your own applications
because the control word is sent to the frequency converter as such.
Speed reference
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
MSB
LSB
This is the Reference 1 to the frequency converter. Used normally as Speed reference. The allowed
scaling is –10000...10000. In the application, the value is scaled in percentage of the frequency area
between the set minimum and maximum frequencies.
Bit definitions
Description
Bit
Value = 0
Value = 1
RUN Stop
Run
DIR Clockwise
Counterclockwise
RST
Rising edge of this bit will reset active fault
RDY
Drive not ready
Drive ready
FLT
No fault
Fault active
W
No warning
Warning active
AREF
Ramping
Speed reference reached
Z
-
Drive is running at zero speed
F -
Flux
Ready