82 • vacon
Commissioning
Telephone: +358-201-2121 • Fax: +358-201-212 205
8
5
Check that all Start/Stop switches connected to the I/O terminals are in Stop-position.
6
Connect the frequency converter to mains.
7
Set the parameters of group 1 according to the requirements of your application. At least
the following parameters should be set:
-
motor nominal voltage
-
motor nominal frequency
-
motor nominal speed
-
motor nominal current
You will find the values needed for the parameters on the motor rating plate.
NOTE! You can also run the Start-up Wizard. See Chapter 7.3 for more information.
8
Perform run test without motor
Perform either Test A or Test B:
A Controls from the I/O terminals:
a)
Turn the Start/Stop switch to ON position.
b)
Change the frequency reference (potentiometer)
c)
Check in the
that the value of Output frequency changes according
to the change of frequency reference.
d)
Turn the Start/Stop switch to OFF position.
B
Control from the control keypad:
a)
Change the control from the I/O terminals to the keypad as advised in Chapter 7.4.3.1.
b)
Push the
Start button
on the keypad
start
.
c)
Move over to the Keypad Control Menu (K3) and Keypad Reference submenu
(Chapter7.4.3) and change the frequency reference using the
+
-
.
d)
Check in the
that the value of Output frequency changes according
to the change of frequency reference.
e)
Push the
Stop button
on the keypad
stop
.