control keypad
vacon 83
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7
7.3.4.3
Fault time data record
When a fault occurs, the information described in Chapter 7.3.3.4 is displayed. By pressing
you will enter the
Fault time data record menu
indicated by T.1
→
T.#. In this menu,
some selected important data valid at the time of the fault are recorded. This feature will help the
user or the service person in determining the cause of the fault.
The data available are:
T.1
Counted operation days
(Fault 43: Additional
code)
(d)
T.2
Counted operation hours
(Fault 43: Counted
operation days)
(hh:mm:
ss)
(d)
T.3
Output frequency
(Fault 43: Counted
operation hours)
Hz
(hh:mm:
ss)
T.4
Motor current
A
T.5
Motor voltage
V
T.6
Motor power
%
T.7
Motor torque
%
T.8
DC voltage
V
T.9
Unit temperature
C
T.10
Run status
T.11
Direction
T.12
Warnings
T.13
0-speed*
Table 7
-
3. Fault time recorded data
* Tells the user if the drive was at zero speed (< 0.01 Hz) when the fault occurred
Real time record
If real time is set to run on the inverter, the data items T1 and T2 will appear as follows:
T.1
Counted operation days
yyyy-mm-dd
T.2
Counted operation hours
hh:mm:ss,
sss