20 vacon
technical data
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
4
4.3
Technical information
Supply
connection
Input voltage U
in
465...800Vdc ( 380-500 Vac)
640...1100Vdc ( 525-690 Vac)
The waviness of the inverter supply voltage, which is
formed in rectification of the electric network's
alternating voltage in basic frequency, must be less
than 50V peak-to-peak.
Input current I
in
(sqrt3 × U
mot
× I
mot
× cos
) / ( U
in
× 0.98)
DC bank capacitance
FI9_5 : 4950
F; FI9_6 : 3733
F
FI10_5: 9900
F; FI10_6: 7467
F
FI12_5: 19800
F; FI12_6: 14933
F
FI13_5: 29700
F; FI13_6: 22400
F
Starting delay
5 s (FI9 and greater)
Motor
connection
Output voltage
3 ~ 0 U
in
/ 1.4
Continuous output
current
IH: Ambient tempe40 °C (104 °F),
overloadability 1.5 x IH (1 min./10 min.).
- 50 °C (104 - 122°F), the ambient
temperatures use derating factor IH*1.5%/1 °C (°F).
55 °C (122 - 131°F), the ambient
temperatures use derating factor IH*2.5% /1 °C (°F).
Starting torque
I
S
for two seconds, torque motor dependent
Peak current
I
S
for 2 s every 20 s
Output frequency
Frequency resolution
Application dependent
Control
characteristics
Control method
Frequency control U/f
Open Loop Sensorless Vector Control
Closed Loop Frequency Control
Closed Loop Vector Control
Switching frequency
(see parameter 2.6.9)
NXI_5:
NXI_6:
Frequency reference
Analogue input
Panel reference
Resolution 0.1% (12-bit), accuracy ±1%
Resolution 0.01 Hz
Field weakening point
Acceleration time
Deceleration time
Braking torque
DC brake: 30% * T
N
(without brake)
Ambient
conditions
Ambient operating
temperature
Storage temperature
-40 °C (-40 °F)...+70 °C (158 °F)
Relative humidity
0 to 95% RH, non-condensing, non-corrosive,
no dripping water
Air quality:
-
chemical fumes
-
solid particles
Designed according to
-3-3, AC drive in operation, class 3C2
-3-3, AC drive in operation, class 3S2
Altitude
100% loadability (no derating) up to 1000 m.
Maximum elevation 2000 m (525-690 VAC) and 4000
m (380-500 VAC), Relay I/O: max. 240 V: 3000 m;
max. 120 V: 4000 m, see Power derating as a
function of installation altitude. See Chapter 4.4.