cabling and connections
vacon 63
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
Figure 6-22. Jumper selection for OPT-A1
WARNING
Ensure that the jumper positions are correct. Running the
motor with signal settings that differ from the jumper positions
will not harm the inverter but may harm the motor.
Note: If you change the AI/AO signal content also remember to changer the corresponding board
parameter in
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
AI1 mode: Voltage input; 0...10V
AI1 mode: Voltage input; 0...10V (differential)
AI1 mode: Voltage input; -10...10V
Jumper block X2:
AI2 mode
AI2 mode : 0...20mA; Current input
AI2 mode: Voltage input; 0...10V
AI2 mode: Voltage input; 0...10V (differential)
AI2 mode: Voltage input; -10...10V
Jumper block X3:
CMA and CMB grounding
CMB connected to GND
CMA connected to GND
CMB isolated from GND
CMA isolated from GND
CMB and CMA
internally connected together,
isolated from GND
= Factory default
Jumper block
X6:
AO1 mode
AO1 mode: 0...20mA; Current output
AO1 mode: Voltage output; 0...10V
AI1 mode: 0...20mA; Current input
Jumper block
X1:
AI1 mode