Process Data OUT (Slave
Master)
The fieldbus master can read the frequency converter’s actual values using process data variables.
Basic, Standard, Local/Remote, Multi-Step, PID control and Pump and fan control
applications use
process data as follows:
Data
Value
Unit
Scale
Process data OUT 1
Output Frequency
Hz
0,01 Hz
Process data OUT 2
Motor Speed
rpm
1 rpm
Process data OUT 3
Motor Current
A
0,1 A
Process data OUT 4
Motor Torque
%
0,1 %
Process data OUT 5
Motor Power
%
0,1 %
Process data OUT 6
Motor Voltage
V
0,1 V
Process data OUT 7
DC link voltage
V
1 V
Process data OUT 8
Active Fault Code
-
-
The
Multipurpose
application has a selector parameter for every Process Data. The monitoring val-
ues and drive parameters can be selected using the ID number (see NX All in One Application Ma-
nual, Tables for monitoring values and parameters). Default selections are as in the table above.
Process Data IN (Master -> Slave)
ControlWord, Reference and Process Data are used with All-in One applications as follows:
Basic, Standard, Local/Remote, Multi-Step applications
Data
Value
Unit
Scale
Reference
Speed Reference
%
0.01%
ControlWord
Start/Stop Com-
mand
Fault reset Com-
mand
-
-
PD1 – PD8
Not used
-
-
Содержание NX OPTCP
Страница 1: ...vacon nx ac drives optcp profinet option board user manual ...
Страница 16: ...16 vacon Installation Tel 358 0 201 2121 Fax 358 0 201 212 205 2 5 Insert power supply 6 Insert CPU ...
Страница 20: ...20 vacon Installation Tel 358 0 201 2121 Fax 358 0 201 212 205 2 13 Change Optioncard properties ...
Страница 43: ......
Страница 44: ...Document ID Rev A ...