Profinet IO
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
2
5.3.1.5.
State Machine
The state machine describes the device status and the possible control sequence of the frequency
converter. The state transitions can be generated by using the “Control word”. The “Status word”
indicates the current status of the state machine. The modes
INIT, STOP, RUN
and
FAULT
corres-
pond to the actual mode of the Frequency converter
General state diagram
Power ON
S1: Switching On Inhibited
ZSW1 bit 6 = True; 0,1,2,”p.e”a=False
S2: Ready For Switching On
ZSW1 bit 0=True; 1,2,6,”p.e”=False
S3: Switched On
ZSW1 bit 0,1=True; 2,6,”p.e”=False
S4: Operation
ZSW1 bit 0,1,2”p,e.”=True; 6=False
OFF
AND No Coast Stop
AND No Quick Stop
STW1 bit0=False
AND bit1=True AND bit2=True
Coast Stop
OR Quick Stop b
AND No Quick Stop
STW1 bit1=False
OR bit2=False
ON
STW1 bit0=True
OFF
STW1 bit0=False
Enable operation
Disable operation
STW1 bit3=True
STW1 bit3=False
Coast stop
STW1 bit1=False
Coast stop
OR Quick stop
STW1 bit1=False
OR bit2=False
ON
STW1 bit0=True
OFF
STW1 bit0=False
Quick stop
STW1 bit2=False
Ramp stop
Disable operation
STW1 bit3=False
Standstill detected
OR
Disable operation
STW1 bit3=False
Quick stop
STW1 bit2=False
Quick stop
S5: Switching Off
ZSW1 bit 0,1”p.e”=True
bit 2,6=False
Coast Stop
Standstill detected
OR
Disable operation
STW1 bit3=False
STW1 bit1=False
Figure 3.
5.3.1.6.
Additional Process data in
ProcessData Master -> Slave
The Master can write max. 8 additional setting values to the device with the help of the Process Data.
How these setting values are used is totally dependent on the application in use.
5.3.1.7.
Additional Process data out
ProcessData Slave -> Master
The master can read the frequency converter’s actual values using the process data variables. De-
pending on the used application, the contents are either standard or can be selected with a parame-
ter.
Содержание NX OPTCP
Страница 1: ...vacon nx ac drives optcp profinet option board user manual ...
Страница 16: ...16 vacon Installation Tel 358 0 201 2121 Fax 358 0 201 212 205 2 5 Insert power supply 6 Insert CPU ...
Страница 20: ...20 vacon Installation Tel 358 0 201 2121 Fax 358 0 201 212 205 2 13 Change Optioncard properties ...
Страница 43: ......
Страница 44: ...Document ID Rev A ...