24
• vacon
Commissioning
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
2
NOTE!
If the fieldbus cable is broken at the Ethernet board end or removed a fieldbus error is immediately
generated.
All Ethernet parameters are saved to the Ethernet board (not to the control board). If the Ethernet
board is replaced by a new one you must re-configure the new Ethernet board. Option board para-
meters can also be saved to the keypad using the NCIPConfig tool or the NCDrive.
4.4.
Start-up test
In the AC drive application:
Choose Fieldbus (Bus/Comm) as the active control place (see Vacon NX User's Manual, Chapter
7.3.3).
In the Master software:
1.
Set Control Word value to 0hex.
2.
Set Control Word value to 47Ehex.
3.
Set Control Word value to 47Fhex.
4.
Frequency converter status is RUN.
5.
Set Reference value to 5000 (=50.00%).
6.
The Actual value is 5000 and the frequency converter output frequency is 25.00 Hz.
7.
Set Control Word value to 477hex.
8.
Frequency converter status is STOP.