36 • vacon
metasys n2
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
7
7.3
N2 POINT MAP
7.3.1
Analogue Inputs (AI)
NPT
NPA
Description
Units
Note
AI
1
Speed Setpoint
Hz
2 decimals
AI
2
Output Speed
Hz
2 decimals
AI
3
Motor Speed
Rpm
0 decimal
AI
4
Load (power)
%
1 decimal
AI
5
Megawatt Hours
MWh
Total Counter
AI
6
Motor Current
A
2 decimal
AI
7
Bus Voltage
V
0 decimal
AI
8
Motor Volts
V
1 decimal
AI
9
Heatsink Temperature
°
C
0 decimal
AI
10
Motor Torque
%
1 decimal
AI
11
Operating Days (trip)
Day
0 decimal
AI
12
Operating Hours (trip)
Hour
0 decimal
AI
13
Kilowatt Hours (trip)
kWh
Trip Counter
AI
14
Torque Reference
1)
%
1 decimal
AI
15
Motor Temperature
Rise
1)
%
1 decimal
AI
16
FBProcessDataOut1
2)
-32768 to
+32767
0 decimal
AI
17
FBProcessDataOut2
2)
-32768 to
+32767
0 decimal
AI
18
FBProcessDataOut3
2)
-32768 to
+32767
0 decimal
AI
19
FBProcessDataOut4
2)
-32768 to
+32767
0 decimal
AI
20
FBProcessDataOut5
2)
-32768 to
+32767
0 decimal
AI
21
FBProcessDataOut6
2)
-32768 to
+32767
0 decimal
AI
22
FBProcessDataOut7
2)
-32768 to
+32767
0 decimal
AI
23
FBProcessDataOut8
2)
-32768 to
+32767
0 decimal
Table 19.
1)
Torque Reference (AI-14) and Motor Temperature Rise (AI-15) NOT supported in NXL
2)
These analogue inputs are application specific.