26 • vacon
modbus
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
6
Process Data Master -> Slave
(max 22 bytes)
ID
Modbus register
Name
Range/Type
2001
32001, 42001
FB Control Word
Binary coded
2002
32002, 42002
FB General Control Word
Binary coded
2003
32003, 42003
FB Speed Reference
0…10000 %
2004
32004, 42004
FB Process Data In 1
Integer 16
2005
32005, 42005
FB Process Data In 2
Integer 16
2006
32006, 42006
FB Process Data In 3
Integer 16
2007
32007, 42007
FB Process Data In 4
Integer 16
2008
32008, 42008
FB Process Data In 5
Integer 16
2009
32009, 42009
FB Process Data In 6
Integer 16
2010
32010, 42010
FB Process Data In 7
Integer 16
2011
32011, 42011
FB Process Data In 8
Integer 16
Table 11.
The use of process data depends on the application. In a typical situation, the device is started and
stopped with the ControlWord (CW) written by the Master and the Rotating speed is set with Refer-
ence (REF). With PD1…PD8 the device can be given other reference values (e.g. Torque reference).
With the StatusWord (SW) read by the Master, the status of the device can be seen. Actual Value (ACT)
and PD1…PD8 show the other actual values.
6.2.3
Process data in
This register range is reserved for the control of the frequency converter.
Process data in
is located in
range ID 2001…2099. The registers are updated every 10 ms. See Table 12.
ID
Modbus register
Name
Range/Type
2001
32001, 42001
FB Control Word
Binary coded
2002
32002, 42002
FB General Control Word
Binary coded
2003
32003, 42003
FB Speed Reference
0…10000 %
2004
32004, 42004
FB Process Data In 1
Integer 16
2005
32005, 42005
FB Process Data In 2
Integer 16
2006
32006, 42006
FB Process Data In 3
Integer 16
2007
32007, 42007
FB Process Data In 4
Integer 16
2008
32008, 42008
FB Process Data In 5
Integer 16
2009
32009, 42009
FB Process Data In 6
Integer 16
2010
32010, 42010
FB Process Data In 7
Integer 16
2011
32011, 42011
FB Process Data In 8
Integer 16
Table 12. Fieldbus basic input table