vacon • 26
Active Front End (AFE)
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4.5
LCL filter technical data
Table 5. Technical specifications for Vacon LCL filter for Active Front End units
AC connections
Voltage U
in
Same as the unit
Frequency f
in
50 or 60 Hz +2%
Continuous output current
Same as the unit
Switching frequency
LCLxxxx 5: 3.6 kHz
LCLxxxx 6: 3.6 kHz
Cooling fan With
integrated DC/DC-
power supply
Input voltage U
in
333...911 Vdc; 460...1200 Vdc
Power consumption
220 W
Losses
20…30 W
Short-circuit protection
DC fuses on the input side
Cooling fan with
external DC-power
supply
Input voltage U
in
48 Vdc; -10...+10%
Current
5 A
Short-circuit protection
AC fuses on the input side of the external
power supply.
EMC (using factory
settings)
Immunity
EN 61800-3 (2
nd
edition 2004), second
environment.
Safety
Same as the unit
Ambient conditions
Ambient temperature during
operation
Same as the unit
Storage temperature
Same as the unit
Relative humidity
Same as the unit
Air quality:
-
Chemical fumes
-
Solid particles
Same as the unit
Elevation of place of operation
Same as the unit
Vibration
EN 50178/EN 60068-2-6
Same as the unit
Impacts
EN 50178, EN 60068-2-27
Same as the unit
Dissipation power
Approximately 1%
Protection
Cooling fan rotation monitoring
Yes (with integrated DC/DC power supply)
Over-temperature monitoring
Yes