10 • vacon
Lift Application – Parameter lists
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
3.8
Output signals (Control keypad: Menu P2
Æ
P2.7)
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.7.1
0 16 2
313
0=Not used
1=Ready
2=Run
3=Fault
4=Fault inverted
5=FC overheat warning
6=Ext. fault or warning
7=Not Used
8=Warning
9=Reversed
10=Preset speed
11=At speed
12=Mot. regulator active
13=OP freq. limit superv.1
14=Control place: IO
15=Thermistor fault/ warn
16=Mechanical brake
P2.7.2
0 16 3
490
As
parameter
2.7.1
P2.7.3
0 16 16
314 As
parameter
2.7.1
P2.7.4
0 16 1
312 As
parameter
2.7.1
P2.7.5
0 9 1
307
0=Not used
1=Output freq. (0—f
max
)
2=Freq. reference (0—f
max
)
3=Motor speed (0–Motor
nominal speed)
4=Output current (0—I
nMotor
)
5=Motor torque (0—T
nMotor
)
6=Motor power (0—P
nMotor
)
7=Motor voltage (0--U
nMotor
)
8=DC-link volt (0—1000V)
9=Digital output 2
P2.7.6
0,00 10,00 S 1,00
308
0=No filtering
P2.7.7
0 1 0
309
0=Not inverted
1=Inverted
P2.7.8
0 1 0
310
0=0 mA
1=4 mA
P2.7.9
10 1000 % 100
311
P2.7.10
0 2 0
315
0=No limit
1=Low limit supervision
2=High limit supervision
P2.7.11
0,00 Max
Freq
Hz
0,00
316
Table 3- 9. Output signals, P2.7