38 • vacon
description of parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
Parameters 2.8.14-2.8.17, other protections:
2.8.14
Response to thermistor fault
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to
3 = Fault, stop mode after fault always by coasting
2.8.15
Response to fieldbus fault
Set here the response mode for the fieldbus fault if a fieldbus board is used. For more
information, see the respective Fieldbus Board Manual.
See
2.8.16
Response to slot fault
Set here the response mode for a board slot fault due to missing or broken board.
See
2.8.17
Minimum current limit
If actual current of the motor is below the minimum current limit fault is activated. The
fault is activated only when the mechanical brake is open.