30 • vacon
description of parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
2.7 OUTPUT
SIGNALS
2.7.1
Relay output 1 function
2.7.2
Digital output 2 (Analogue output 1) function
2.7.3
Expander board relay output 1 function
2.7.4
Expander board digital output 1 function
Setting value
Signal content
0 = Not used
Out of operation
Relay output RO1 and expander board
programmable relays (RO1, D01) are activated when:
1 = Ready
The frequency converter is ready to operate
2 = Run
The frequency converter operates (motor is running)
3 = Fault
A fault trip has occurred
4 = Fault inverted
A fault trip not occurred
5 = Frequency converter overheat
warning
The heat-sink temperature e70
°
C
6 = External fault or warning
Fault or warning depending on par. 2.8.1
7 = Not Used
Not Used
8 = Warning
Always if a warning exists
9 = Reversed
The reverse command has been selected
10 = Preset speed
A preset speed has been selected
11 = At speed
The output frequency has reached the set reference
12 = Motor regulator activated
Overvoltage or overcurrent regulator was activated
13 = Output frequency limit 1
supervision
Not used in this application
14 = Control from I/O terminals
Selected control place (Menu K3; par. 3.1) is “I/O
terminal”
15 = Thermistor fault or warning
The thermistor input of option board indicates
overtemperature. Fault or warning depending on
parameter 2.8.14
16 = Mechanical brake
External brake ON/OFF control
(see parameter Group G2.3)
Table 4-4. Output signals via RO1, DO2 and expander board RO1, and DO1.
2.7.5
Analogue output function
This parameter selects the desired function for the analogue output signal.
See the table on page 10 for the parameter values. Maximum analogue output is
activated when output selected by