using macro mode and getting a quick start
vacon
50
24-hour s358 (0)40 837 1150 • Email: [email protected]
6
490 Appl Macro
Default: Factory
Range: Text string
Macro
This parameter configures what macro will be active in the drive. A macro will change
a default or visibility of a parameter.
The following data values may be assigned to this parameter:
Macro
Description
Factory
Provides a simple way to restore factory default parame-
ter listings.
Fan
Provides a basic set-up for Fan applications, including V/
Hz curve and terminal strip operation in Level 1 program-
ming.
Fan w/PI
Provides a simple set-up for Fan applications that require
process control. Parameters such as V/Hz curve, terminal
strip operation, and PI configuration are available in Level
1 programming.
Pump
Provides a basic set-up for Pump applications, including
V/Hz curve and terminal strip operation in Level 1 pro-
gramming.
Pump w/PI
Provides a simple set-up for Pump applications requiring
process control. Parameters such as V/Hz curve, terminal
strip operation, and PI configuration are available in Level
1 programming.
Vector
Activates the sensorless vector control algorithm. When
an operation requires low speed and high torque, this
macro should be activated. Note that in Vector control,the
drive automatically runs the the Motor Rs measurements
when leaving PROGram mode.
491 Seq Appl
Default: Disabled
Range: Text string
Macro
This parameter configures sequencer parameters are visible and the time base of the
sequencer. The time base may change depending on the timing loops used.
The following data values may be assigned to this parameter:
Macro Value
Description
Disabled
Sequencer disabled and parameters hidden.
1sec Base
Sequencer enabled and 1 second time base.
.1sec Base
Sequencer enabled and 0.1 second time base.
.01sec Base
Sequencer enabled and 0.01 second time base.
492 SIO Visible
Default: No
Range: Text string
Macro
This parameter configures whether SIO parameters are visible.
The following data values may be assigned to this parameter:
Macro Value
Description
No
SIO parameters hidden
Yes
SIO parameters visible
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......