Communications
vacon • 32
24-hour s358 (0)40 837 1150 • Email: [email protected]
6
6.3.3.4
ID map
Using the ID map, you can read consecutive memory blocks that contain parameters whose
ID's are not in a consecutive order. The address range 10501 - 10530 is called 'IDMap', and it
includes an address map in which you can write your parameter ID's in any order. The address
range 10601 to 10630 is called 'IDMap Read/Write,' and it includes values for parameters writ-
ten in the IDMap. As soon as one ID number has been written in the map cell 10501, the corre-
sponding parameter value can be read and written in the address 10601, and so on.
Table 22. IDMap initialization
Once the IDMap address range has been initialized with any parameter ID number, the param-
eter value can be read and written in the IDMap Read/Write address range address IDMap ad-
dress + 100.
Table 23. Parameter Values in 16-bit IDMap Read/Write registers
If the IDMap table has not been initialized, all fields show the index '0'. If the it has been initial-
ized, the parameter ID's included in it are stored in the flash memory of the OPT-CI board.
Address
Data
410601
Data included in parameter ID700
410602
Data included in parameter ID702
410603
Data included in parameter ID707
410604
Data included in parameter ID704
Address
Data
410501
700
410502
702
410503
707
410504
704
Parameter ID’s
ID
699
700
701
702
703
704
705
706
707
708
Содержание 100 INDUSTRIAL
Страница 1: ......
Страница 3: ...vacon 1 Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 7: ...1 vacon 5 Safety Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 11: ...3 vacon 9 Modbus technical data Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 27: ...5 vacon 25 Programming Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 43: ...7 vacon 41 Fault tracing Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 45: ...8 vacon 43 Quick setup Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 47: ......