6
vacon • 27
Communications
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
6.3
Modbus data mapping
6.3.1
Coil registers
Coil registers contain binary data (Read/Write). See page 29.
Table 13. Defined coil registers
6.3.2
Input discrete registers
Input discrete registers contain binary data (Read). See page 31.
Table 14. Defined Input Discrete
6.3.3
Holding and input registers
All values can be read with function codes 3 and 4 (all registers are 3X and 4X reference). Mod-
bus registers are mapped to drive ID’s as follows:
Address
Function
Purpose
0001
RUN/STOP
Control Word, bit 0
0002
Direction
Control Word, bit 1
0003
Fault reset
Control Word, bit 2
Address
Function
Purpose
10001
Ready
Status Word, bit 0
10002
Run
Status Word, bit 1
10003
Direction
Status Word, bit 2
10004
Fault
Status Word, bit 3
10005
Alarm
Status Word, bit 4
10006
At reference
Status Word, bit 5
10007
Zero speed
Status Word, bit 6
10008
Flux ready
Status Word, bit 7
Address
range
Purpose
Access
type
See
0001 - 2000
Vacon Application ID´s
16bit
2001 - 2050
FBProcessDataIN
16bit
2051 - 2099
FBProcessDataIN
32bit
2101 - 2150
FBProcessDataOUT
16bit
2151 - 2199
FBProcessDataOUT
32bit
Содержание 100 INDUSTRIAL
Страница 1: ......
Страница 3: ...vacon 1 Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 7: ...1 vacon 5 Safety Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 11: ...3 vacon 9 Modbus technical data Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 27: ...5 vacon 25 Programming Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 43: ...7 vacon 41 Fault tracing Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 45: ...8 vacon 43 Quick setup Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 47: ......